background image

KNX-USB 

SATEL 

 information on the progress of writing data from interface non-volatile memory to a file. 

Buttons 

Start logging

 

–  click to enable bus logging mode in the interface. 

Stop logging

 

–  click to disable bus logging mode in the interface. 

Clear memory

 

–  click to clear the non-volatile memory of the interface. 

Export to file

 

–  click to start exporting data from the non-volatile memory of the interface 

to a file. The window will open in which you can give a name and choose 
the format (CSV or XML) and file location. 

5.  Specifications 

Power supply 

USB voltage .................................................................................................................... 5 VDC 

Current consumption from USB ................................................................................... < 30 mA 

Maximum power consumption from USB ..........................................................................0.3 W 

Type of USB connector .................................................................................... mini USB type B 

KNX bus voltage .................................................................................................... 

20…30 VDC 

Current consumption from KNX bus ............................................................................ < 20 mA 

Maximum power consumption from KNX bus ...................................................................0.6 W 

Other parameters 

Maximum length of USB cable ............................................................................................. 5 m 

Operating temperature range ................................................................................. -5

°C...+45°C 

Storage/transport temperature range ................................................................... -25

°C...+70°C 

IP code ............................................................................................................................... IP20 

Enclosure dimensions ..................................................................................... 67 x 34 x 21 mm 

Weight ............................................................................................................................... 108 g 

 

 

Summary of Contents for KNX-USB

Page 1: ...KNX USB KNX USB interface Firmware version 1 00 knx usb_en 11 19 SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu ...

Page 2: ...ve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Please visit us at http www satel eu The declaration of conformity may be consulted at www satel eu ce The following symbols may be used in this manual note caution ...

Page 3: ...tion saved in the KNX USB interface memory allows you to reproduce the telegram traffic on the KNX bus in off line mode You can download the KNX USB Soft program from www satel eu 1 Features Communication with the KNX bus via integrated bus connector Power supply from the KNX bus or from the computer USB port Galvanic isolation of the KNX system and computer Data transmission between the interface...

Page 4: ...omputer s operating system Microsoft Windows In the ETS program the interface will be added to the list of devices connected to the bus Bus Connections Interfaces where you can change its individual address 4 KNX USB Soft program The KNX USB Soft program allows you to switch the KNX USB interface to the bus logging mode in which the log of events generated on the KNX bus is saved to the non volati...

Page 5: ...olatile memory of the KNX USB interface the value was calculated for a telegram type 1 001 Switch Reaching this value does not stop logging Information about events with the oldest date is overwritten with information about events that are currently generated on the KNX bus A power loss turns off the bus logging mode The interface powered from the KNX bus does not charge the energy bank connected ...

Page 6: ...he interface to a file The window will open in which you can give a name and choose the format CSV or XML and file location 5 Specifications Power supply USB voltage 5 VDC Current consumption from USB 30 mA Maximum power consumption from USB 0 3 W Type of USB connector mini USB type B KNX bus voltage 20 30 VDC Current consumption from KNX bus 20 mA Maximum power consumption from KNX bus 0 6 W Othe...

Reviews: