
52 Programming
SATEL
115. A
RMING TYPE STATUS
– active when selected partitions are armed in the selected mode.
116. I
NTERNAL SIREN
– signals the same alarms and violations as the 1. B
URGLARY
or 9. DAY
A
LARM
output type (logic product of the 1. B
URGLARY
and 9.
D
AY
A
LARM
outputs).
117. T
AMPERING STATUS
– informs about tamper of selected zones, keypads and expanders.
118
.
K
EYFOB BATTERY LOW
– informs about low battery in keyfobs belonging to selected
users. Refers to the 433 MHz keyfobs (supported by the INT-RX or INT-RX-S modules) or
the APT-100 keyfobs (supported by the ABAX system).
119
.
W
IRELESS SYSTEM JAMMING
– indicates the jamming of device supporting the ABAX
wireless system (INTEGRA 128-WRL control panel, ACU-100 or ACU-250 controllers).
120. T
HERMOSTAT
– active when the temperature measured by ATD-100 wireless detectors
drops below the specified temperature threshold. See also section 120. T
HERMOSTAT
OUTPUT PARAMETERS
p. 53.
121. M
ASKING
– signals for a programmed time masking the detectors connected to the 3EOL
zones.
122. M
ASKING STATUS
– indicates the masking the detectors connected to the 3EOL zones.
4.3 Options
Polarity
– defines the output operating mode (see Table 5).
high-current output
option enabled
(normal polarity)
option disabled
(reversed polarity)
active status
+12V voltage supply
+12V voltage cut-off
inactive status
+12V voltage cut-off
+12V voltage supply
low-current output
option enabled
(normal polarity)
option disabled
(reversed polarity)
active status
shorted to ground
isolated from ground
inactive status
isolated from ground
shorted to ground
Table 5. Functioning of outputs, depending on the P
OLARITY
option.
Pulsating
– the option refers to timed outputs. If it is enabled, the output operates in
a pulsating mode (0.5/0.5 s). If it is disabled, the output operates continuously.
Latch
– the option refers to alarm outputs. If it is enabled, the output will be active until the
alarm is cleared by the user.
Active during violation
– the option applies to the 24. MONO
SWITCH
output. If enabled, the
output is always active when a control zone is violated, and the countdown of output cut-
off time will only be running after the violation ends.
Timer activates/deactivates
– the option applies to the 24. MONO
SWITCH
and 25. BI
SWITCH
outputs. If enabled, the output can be controlled by selected timers. Turning the timer ON
activates the output (in case of the 24. MONO
SWITCH
type output – for a programmed
time), and turning the timer OFF deactivates the output.
Not controlled by arming
– the option refers to the 105. S
HUTTER UP
and 106. S
HUTTER
DOWN
type outputs. If enabled, the partition arming / disarming has no effect on the output
status.
4.4 Output triggering
Zones
– indicate the zones. The output will be controlled by events related to these zones.