Satel INT-R Manual Download Page 1

®

 

UNIVERSAL EXPANDER  

FOR CARD / CHIP READERS 

INT-R 

int-r_en 09/11 

The INT-R expander interfaces with the INTEGRA and CA-64 alarm control panels, replacing 
the previously offered CA-64 SR and CA-64 DR expanders. This manual applies to the 
expander with electronics version 2.0 and firmware version 3.00 (or later). 

1. Features 

  Support for two proximity card / DALLAS chip readers. 

  Support for WIEGAND 26 interface readers. 

  Capability to arm / disarm and clear alarm by using the readers. 

  Capability to implement access control function – control of a single door. 

  Relay to control the electromagnetic door lock. 

  Input for door status control. 

  Input for door unlocking with a button. 

  Capability to automatically unlock the door in case of fire alarm. 

  Additional NC type tamper input. 

2.  Installation and start-up 

Disconnect power before making any electrical connections. 

The expander is designed for indoor installation, in spaces with normal air humidity. 
1.  Secure the expander board in its enclosure. 
2. Determine the expander operating mode (see: S

ELECTING THE EXPANDER

 

OPERATING 

MODE

). 

3.  With the DIP-switches, set the appropriate expander address. To set an address, use the 

switches 1-5. The address must be different from that in the other modules connected to 
the expander bus. The address is the sum of numerical values set on the switches 1-5 
(see Table 1). 

 

Switch number 

1 2 3 4 5 

Numerical value 

1 2 4 8 16 

Table 1. Numerical values corresponding to the switches set to ON position (in the OFF 

position, the value 0 is assigned to each switch) 

 
4.   Connect the CLK, DTA and COM terminals with wires to the appropriate terminals of the 

control panel expander bus. To make a connection, it is recommended to use an 
unscreened straight-through cable. When using the twisted-pair type of cable, the CLK 
(clock) and DTA (data) signals must not be sent through one twisted pair. The wires must 
be run in one cable. The cable length should not exceed 1000 m. If it exceeds 300 
meters, it may be necessary to use several wires connected in parallel for each signal. 

5.  Connect readers to the respective terminals (see: C

ONNECTING THE READERS

). 

6.  Connect the door status control detector to the IN and COM terminals. 

Summary of Contents for INT-R

Page 1: ...Determine the expander operating mode see SELECTING THE EXPANDER OPERATING MODE 3 With the DIP switches set the appropriate expander address To set an address use the switches 1 5 The address must be...

Page 2: ...power source which is located at a closer distance a power supply unit or an expander with power supply 11 Turn on the power 12 Start the identification function in the control panel Depending on the...

Page 3: ...perating mode The device can operate as I CA 64 SR expander supporting the CZ EMM readers CZ EMM CZ EMM2 CZ EMM3 and CZ EMM4 manufactured from May 2005 factory default setting II CA 64 SR expander sup...

Page 4: ...r B Terminal description Color of reader wire GA GB 12 V DC power supply red SIG1A SIG1B data 0 green SIG2A SIG2B data 1 black COM COM common ground blue BPA BPB sound control BEEPER yellow LD1A LD1B...

Page 5: ...d DALLAS chip the relay is active for the RELAY ON TIME Fixed ON time OFF if door open ON open off after reading the code of proximity card DALLAS chip the relay is active until the door is opened the...

Page 6: ...the 93 UNAUTHORIZED ACCESS type output Alarm on unauth access Unauth alarm this option is available when the AUTHORIZATION CONTROL is enabled If both options are enabled and the partition to which th...

Page 7: ...e of the BI OUTPUTS type you can control the outputs of 25 BI SWITCH type Control MONO output MONO outs ctr using the card chip assigned to a code of the MONO OUTPUTS type you can activate the 24 MONO...

Page 8: ...holding the card chip the WIEGAND 26 interface readers do not support the card holding function When read out the card chip code is transmitted through the expander to the control panel It is the con...

Page 9: ...tarting the arming procedure which is equivalent to arming if no exit delay has been programmed for the partition disarming and or alarm clearing 4 short blinks and 1 long blink confirmation of turnin...

Page 10: ...card chip should change the code 3 short beeps depending on the current partition status starting the arming procedure which is equivalent to arming if no exit delay has been programmed for the parti...

Page 11: ...The declaration of conformity may be consulted at www satel eu ce SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www satel pl...

Reviews: