KNX INTEGRATION MODULE 

INT-KNX

 

 

int-knx_en 09/11 

The INT-KNX module integrates the INTEGRA alarm system with the KNX system, so the 
control panel can control the actuators connected to the KNX bus, and the bus devices can 
control the alarm system. The module interfaces with the INTEGRA control panels with 
software version 1.10 or later. This manual applies to the module with electronics version 1.2. 

Note:

 The INT-KNX module has no integrated Bus Coupling Unit (BCU). The BCU in BTM 

version must be purchased separately (e.g. Bus Coupling Unit (BTM) UP117/11 made 
by Siemens). 

1. Features 

  Expansion of the alarm system by adding virtual outputs dedicated to control actuators 

connected to the KNX bus. 

  The number of virtual outputs determined by means of DIP switches (from 8 to 64 – a 

multiple of 8). 

  Sending a predefined telegram after changing the virtual output status. 

  The status of virtual outputs automatically changes with changing the status of 

communication objects having the same group address as the output. 

  Capability to control the KNX system with macro commands available in the INT-KSG 

keypad, without using the virtual outputs. 

  Receiving commands sent by the bus devices and sending them to the alarm system 

zones (support for "On" and "Off" commands). 

  RS-232 port for connecting the module to the BCU. 

  Dedicated adapter (interface) and cable for connecting the module to the BCU. 

2. Installation 

Disconnect power before making any electrical connections. 

The INT-KNX module should be installed indoors, in spaces with normal air humidity. 
1.  Secure the module electronics board in its enclosure. 
2.  Using the DIP switches, set the appropriate address for the module and determine the 

number of outputs that will be added to the system (see: DIP

 SWITCHES

). 

3.  Connect the CK, DT and COM terminals with wires to the appropriate terminals of the 

control panel expander bus. To make a connection, it is recommended to use an 
unscreened straight-through cable. When using the twisted-pair type of cable, the CK 
(clock) and DT (data) signals must not be sent through one twisted pair. The wires must 
be run in one cable. The cable length should not exceed 1000 m. If it exceeds 300 
meters, it may be necessary to use several wires connected in parallel for each signal. 

4.  Connect the tamper switch wires of the enclosure where the module is installed to the 

TMP and COM terminals. If the status of tamper switch is not to be controlled by the 
module, short-circuit the TMP and COM terminals. 

5.  Connect the power leads to the +12 V and COM terminals. If the distance to the control 

panel is less than 300 meters, the module can be supplied directly from the control panel. 

Summary of Contents for INT-KNX

Page 1: ...support for On and Off commands RS 232 port for connecting the module to the BCU Dedicated adapter interface and cable for connecting the module to the BCU 2 Installation Disconnect power before maki...

Page 2: ...battery presence by periodically lowering the voltage make sure that the battery is present for correct operation of the INT KNX module 6 Install and connect the BCU to the KNX bus in accordance with...

Page 3: ...ion with the control panel 3 male socket DB 9 RS 232 port to connect the module to the Bus Coupling Unit BCU using the cable included in the delivery set Description of terminals TMP tamper circuit in...

Page 4: ...outputs 24 1 address is allocated for each group of 8 outputs on the expander bus The module can occupy up to 8 addresses on the expander bus The control panel assigns consecutive addresses to the mo...

Page 5: ...e module with the DLOADX program use the Read button to read data from the module see Fig 5 The program can suggest reading the data itself when you click on the module name in the Structure window Ha...

Page 6: ...sent after activating deactivating the output Telegram type depending on the selected telegram type 0 Toggle on activating the output a telegram with On command is sent and on deactivating the output...

Page 7: ...the Off command by the INT KNX module and the zone restore will occur on receiving a telegram with the On command Note The data are not read from written to the module when using the and buttons in t...

Page 8: ...The declaration of conformity may be consulted at www satel eu ce SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www satel pl...

Reviews: