Satel INT-AV Manual Download Page 3

SATEL INT-AV 

3.2  DIP-switches 

The DIP-switches from 1 to 5 are used to set the address. A numerical value is assigned to 
each switch (in ON position – see Table 1; in OFF position – 0). The sum of these numerical 
values corresponds to the address set. The DIP-switches allow for setting addresses in the 0 
to 31 range. 
 

DIP-switch number 

1 2 3 4 5 

Numerical value

 

1 2 4 8 16 

Table 1. Numerical values assigned to DIP-switches in ON position. 

 
Position of the switch 6 is irrelevant. 
The switches 7 and 8 are used to determine the control panel to which the module is 
connected: 

  module connected to the INTEGRA 128-WRL control panel – both switches must be set 

in ON position; 

  module connected to another INTEGRA / INTEGRA Plus control panel – both switches 

must be set in OFF position. 

4.  Installation 

Disconnect power before making any electrical connections. 

The INT-AV module and INT-AVT terminals should be installed indoors, in spaces with 
normal air humidity. 

4.1  Installing the INT-AV module 

1.  Secure the module in the control panel enclosure. 
2.  Connect the CLK and DTA terminals to the corresponding terminals of the control panel 

communication bus. It is recommended that unscreened straight-through cable be used to 
make the connection. 

3.  Connect the PIN5 plug to the socket on the control panel electronics board (socket to 

connect a voice synthesizer). 

4.  Screw the wires connecting the module with the INT-AVT unit, as required. The way of 

connecting the screw terminals of INT-AVT unit and module is illustrated in Fig. 2. Using a 
straight-through unscreened cable is recommended. The permissible distance between 
the communication terminal and the module is 100 m. 

Note: Resistance of the wires connecting the INT-AVT unit with the INT-AV module has an 

effect on the audio playback volume (the higher the resistance, the lower the volume) 
and the current consumption. 

5.  Use the DIP-switches to set the module address and determine the control panel to which 

the module is connected. 

Summary of Contents for INT-AV

Page 1: ...odule works with the INTEGRA INTEGRA Plus control panels firmware version 1 12 or newer This manual applies to the module electronics version 1 4 and firmware version 1 00 or newer Notes Only one INT...

Page 2: ...anel ON no communication with the control panel sockets for connecting the INT VG voice module CA 64 SM voice synthesizer expander or SM 2 synthesizer RS 232 port TTL standard for updating the module...

Page 3: ...should be installed indoors in spaces with normal air humidity 4 1 Installing the INT AV module 1 Secure the module in the control panel enclosure 2 Connect the CLK and DTA terminals to the correspond...

Page 4: ...The cover will still be connected to the base by the speaker wires When opening the INT AVT terminal enclosure be careful not to rip off the speaker attached to the base Any changes in the constructio...

Page 5: ...e also for presence of the INT AVT terminals connected to the module Disconnecting the module from communication bus changing the position of DIP switches swapping the module with another one in which...

Page 6: ...MF tone by the control panel If this option is disabled alarm verification by the monitoring operator station will only be possible after entering the code The option is available if the VERIF AFTER R...

Page 7: ...option is enabled the module can be operated by means of DTMF commands compliant with SATEL standard and if it is disabled by means of DTMF commands compliant with SIA standard All command are describ...

Page 8: ...l the telephone number of control panel Hang up after the number of rings programmed by the installer Call again within three minutes The call will be answered by the control panel immediately Establi...

Page 9: ...es session and returns to phone answering function if the INT VG module is connected to the control panel returns to the voice menu 88 8 Terminates session with call back for station operator 99 0 Ter...

Page 10: ...es session Cancels first digit of a 2 digit command 0 0 Activates the level 0 command set 1 1 Activates the level 1 command set 8 Updating module firmware When a new version of the module firmware com...

Page 11: ...SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 58 320 94 00 info satel pl www satel eu...

Reviews: