18 CSP-204
●
CSP-208
●
CSP-104
●
CSP-108
SATEL
8. Screw in the screw fixing the cover of power supply
terminals.
5.2.9 Backup power supply
A 12 V sealed lead-acid battery should be used as the backup power source. A battery of
max. 17 Ah capacity can be installed in the control panel enclosure. The control panel can be
used with up to 24 Ah capacity battery (in an external battery box).
The battery must be connected to the dedicated leads (positive terminal to RED lead,
negative terminal to BLACK lead).
If the battery voltage drops under load below 11.5 V, the control panel will signal a battery
fault. When the voltage drops to approx. 10.5 V, the battery will be disconnected.
6. Access levels
The control panel offers three access levels, at which different functions are available. On the
repeater panel, only levels 1 and 2 are available.
6.1 Level 1 – all users
The
,
and
buttons [control panel] or the
button [repeater panel] can be used.
In the case of control panels and repeater panels equipped with LCD display, the
,
,
and
buttons are also available, which allow to open and use the user menu (the
clock programming is not available).
6.2 Level 2 – authorized users
All buttons are available for use. In order to get access at level 2, turn the key switch to
position marked with the symbol.
Note: The control panel cannot be operated at the level 2 at the same time from the control
panel and from the repeaters panel, hence:
turning the control panel key switch will always result in getting access at level 2
(access level 2 on the repeater panel is automatically exited);
getting access at level 2 from the repeater panel is impossible, if operation at level 2
is available on the control panel.