![Satel ASD-200 Quick Start Manual Download Page 3](http://html.mh-extra.com/html/satel/asd-200/asd-200_quick-start-manual_1200919003.webp)
The ASD-200 multisensor detector can detect the early stages of fire development when
there is some visible smoke and/or temperature rise. It is designed for operation within the
ABAX 2 / ABAX two-way wireless system. This manual applies to the detector with firmware
version 1.00, which is supported by:
ABAX
2:
– ACU-220
/
ACU-280 controller,
– ARU-200 repeater.
ABAX:
– ACU-120 / ACU-270 controller (firmware version 5.04 or newer),
– ARU-100 repeater (firmware version 2.02 or newer),
– INTEGRA 128-WRL control panel (firmware version 1.19 or newer and firmware
version of processor used to operate ABAX system 3.10 or newer).
The detector is not a construction product as defined in Regulation (EU) No 305/2011
of the European Parliament and of the Council of 9 March 2011.
1
Features
Visible smoke sensor.
Detection of optical chamber fouling.
Heat
sensor.
Built-in
sounder.
Red LED for optical signaling.
Test
feature.
Battery status control.
“ECO” option for longer battery life (ABAX 2 system only).
Encrypted two-way radio communication in the 868 MHz frequency band (AES standard
for the ABAX 2 system).
Transmission channel diversity – 4 channels for automatic selection of the one that will
enable transmission without interference with other signals in the 868 MHz frequency
band (ABAX 2 system only).
Remote update of detector firmware (ABAX 2 system only).
Tamper protection against enclosure opening.
2
Description
Radio communication
The detector connects to the controller / control panel at regular time intervals to provide
information about its state (periodical communication). Additional communication takes place
in the case of alarm (smoke / high temperature is sensed by the detector) or tamper (tamper
switch has been opened) and after restore of alarm (smoke / high temperature is sensed no
more by the detector) or tamper (tamper switch has been closed).