WIRELESS SMOKE AND HEAT DETECTOR 

asd110_en 10/11 

The ASD-110 multisensor detector can detect the early stages of fire development when 
there is some visible smoke and/or temperature rise. It can operate as a stand-alone device 
or as part of the ABAX two-way wireless system. It is supported by the ACU-100 controller 
with firmware version 3.02 (or later) and by the INTEGRA 128-WRL control panel with 
firmware version 1.10 (or later). 

1. Features 

  EN54-7 compliant visible smoke sensor. 

  EN54-5 compliant heat sensor. 

  Red LED for optical signaling. 

 Built-in sounder. 

 Test feature. 

  Tamper switch (supervised when working in the ABAX system). 

2. Functional description 

An optical method is used for the detection of visible smoke. When the concentration of 
smoke in the optical chamber exceeds a given threshold, an alarm is triggered. The smoke 
sensor operating parameters are modified depending on the temperature changes recorded 
by the heat sensor (thermistor). 
The heat sensor operates according to the requirements of Class A1R (EN 54-5). The alarm 
will be triggered after exceeding a certain threshold temperature (54°C - 65°C) or in the event 
when the temperature rises too rapidly (see Table 1). 

 

Air temperature rise 

velocity 

Lower limit of response 

time 

Upper limit of response 

time 

1 °C/min 

29 min 

40 min 20 s 

3 °C/min 

7 min 13 s 

13 min 40 s 

5 °C/min 

4 min 9 s 

8 min 20 s 

10 °C/min 

1 min 

4 min 20 s 

20 °C/min 

30 s 

2 min 20 s 

30 °C/min 

20 s 

1 min 40 s 

Table 1. Response time limits for the heat sensor. 

 

The alarm is indicated visually (LED steady light) and acoustically (intermittent sound) for 2 
minutes. Pressing the test / reset button (designated with the letter A in Figure 1) during the 
alarm will clear the alarm condition. The alarm information is sent to the ACU-100 controller / 
INTEGRA 128-WRL control panel. After the alarm causes cease to exist, information about 
the alarm end will be sent. 
After starting the test mode in the ABAX system, the LED indicates as follows: 

  flashing quickly – the memory of alarm triggered by smoke sensor; 

  flashing slowly – the memory of alarm triggered by heat sensor; 

  a single short flash – the detector is being polled (there was no alarm). 