44
Address Point
ID
Description
Options/Range
3
Units
3
Type R/W
Notes
+44,45 0x3416
I2 Current THD
0-9999
×
0.1%
UINT32 R
5
+46,47 0x3417
I3 Current THD
0-9999
×
0.1%
UINT32 R
5
+48,49 0x3418 I1
K-Factor
10-9999
×
0.1
UINT32 R
5
+50,51 0x3419 I2
K-Factor
10-9999
×
0.1
UINT32 R
5
+52,53 0x341A I3
K-Factor
10-9999
×
0.1
UINT32 R
5
+54,55 0x341B
I1 Current TDD
0-1000
×
0.1%
UINT32 R
5
+56,57 0x341C
I2 Current TDD
0-1000
×
0.1%
UINT32 R
5
+58,59 0x341D
I3 Current TDD
0-1000
×
0.1%
UINT32 R
5
18560-18567
Maximum 1-Cycle Total Values
+0,1 0x3500 Total
kW
-Pmax-Pmax
U3
INT32
R
+2,3 0x3501 Total
kvar
-Pmax-Pmax
U3
INT32
R
+4,5 0x3502 Total
kVA
0-Pmax
U3
UINT32 R
+6,7 0x3503 Total
PF
0-1000
×
0.001
UINT32 R Absolute
value
18688-18693
Maximum 1-Cycle Auxiliary Values
+0,1 0x3600 Not
used
UINT32 R
+2,3 0x3601 In
Current
0-Imax
U2
UINT32 R
+4,5 0x3602 Frequency
0-Fmax
×
0.01Hz
UINT32 R
18816-18849
Maximum Demands
+0,1 0x3700
V1/V12 Maximum volt demand
0-Vmax
U1
UINT32
R
2
+2,3 0x3701
V2/V23 Maximum volt demand
0-Vmax
U1
UINT32
R
2
+4,5 0x3702
V3/V31 Maximum volt demand
0-Vmax
U1
UINT32
R
2
+6,7 0x3703
I1 Maximum ampere demand
0-Imax
U2
UINT32
R
+8,9 0x3704
I2 Maximum ampere demand
0-Imax
U2
UINT32
R
+10,11 0x3705
I3 Maximum ampere demand
0-Imax
U2
UINT32
R
+12,13 0x3706 Not
used
UINT32 R
+14,15 0x3707 Not
used
UINT32 R
+16,17 0x3708 Not
used
UINT32 R
+18,19 0x3709
Maximum kW import sliding window demand
0-Pmax
U3
UINT32
R
+20,21 0x370A
Maximum kvar import sliding window demand
0-Pmax
U3
UINT32
R
+22,23 0x370B
Maximum kVA sliding window demand
0-Pmax
U3
UINT32
R
+24,25 0x3737 Not
used
UINT32 R
+26,27 0x370D Not
used
UINT32 R
+28,29 0x370E Not
used
UINT32 R
+30,31 0x370F
Maximum kW export sliding window demand
0-Pmax
U3
UINT32
R
+32,33 0x3710
Maximum kvar export sliding window demand
0-Pmax
U3
UINT32
R
19008-19031
Maximum Harmonic Demands
+0,1 0x3880
V1/V12 THD demand
0-9999
×
0.1%
UINT32 R
2
+2,3 0x3881
V2/V23 THD demand
0-9999
×
0.1%
UINT32 R
2
+4,5 0x3882
V3/V31 THD demand
0-9999
×
0.1%
UINT32 R
2
+6,7 0x3883 Not
used
UINT32 R
+8,9 0x3884
I1 THD demand
0-9999
×
0.1%
UINT32 R
+10,11 0x3885
I2 THD demand
0-9999
×
0.1%
UINT32 R
+12,13 0x3886
I3 THD demand
0-9999
×
0.1%
UINT32 R