
28
Table 5-24 Relay Operation Status
Operation status
Value
Normal operation
0
Force operate
1
Force release
2
5.12 Min/Max Log
The Min/Max log registers are supported only for compatibility with other models of instruments.
Because the Min/Max log is not time stamped in the PM130, reading these registers returns you
only values of the Min/Max log parameters which you can read directly via extended data
registers (see Table 5-15).
Table 5-25 Min/Max Log Windows Registers
Min/Max log window
Registers (see Table 5-26)
Min/Max log window #1
4174-4181
Min/Max log window #2
4182-4189
Min/Max log window #3
4190-4197
Min/Max log window #4
4198-4205
Min/Max log window #5
4206-4213
Min/Max log window #6
4214-4221
Min/Max log window #7
4222-4229
Min/Max log window #8
4230-4237
Min/Max log window #9
4238-4245
Min/Max log window #10
4246-4253
Min/Max log window #11
4254-4261
Min/Max log window #12
4262-4269
Table 5-26 Min/Max Log Window Registers
Parameter
Offset
Size,
byte
Direction Range
0
2
R
0
Minute
+1
2
R
0
Hour
+2
2
R
0
Day
+3
2
R
0
Month
+4
2
R
0
Year +5
2
R
0
Parameter value
c
+6
+7
4 R
see
Table
5-15
c
The Min/Max parameter value can be read in one or two registers depending on the value
type. For the value length and conversion scales, refer to Table 5-15. The time stamp is not
available in the PM130 and is read as zeros.
Table 5-27 Min/Max Log Mapping Register
Parameter
Address Size,
byte
Direction Range
Min/Max log start parameter
ID for window #1
4172 2 R/W see
Table
5-15
From 1 to 12 adjacent Min/Max log records can be read at a time via the Min/Max log windows. The
starting window #1 can be mapped to any Min/Max log parameter listed in Table 5-15 by writing the
parameter ID to the Min/Max log mapping register. This must be written before reading the Min/Max log
windows. Note that through Min/Max log windows, you can read only adjacent parameters within the same
Min/Max log data group. Reading parameters outside of the selected Min/Max log data group will return
zero.