![Satec AX-8 Installation And Operation Manual Download Page 9](http://html.mh-extra.com/html/satec/ax-8/ax-8_installation-and-operation-manual_1200351009.webp)
6
ANALOG EXPANDER AX-8
PAN
EL
LOCK WASHER
SCREW
Figure 3-2
Wall Mounting
3.2 Electrical Installation
For AX-8 connections to the power supply, communications and analog
outputs, see
Figures
3-3
(RS-422 network) or
3-4
(RS-485 network).
Power Supply
Use a dedicated breaker from a proper power source, from which the unit
can be turned off. All AX-8 analog outputs are provided with an internal
power supply; no external power supply for analog outputs is required.
Communications
The AX-8 is connected on one side to the Powermeter via the RS-422
input, and from the other side, to the multi-drop communication network
via the RS422 or RS-485 output, using the ASCII, Modbus or DNP3.0
protocol.
Communications may be over a distance of up to 1000 meters and at a
baud rate of up to 19,200 bps. A twisted pair cable of 0.33mm
2
/22AWG is
recommended.