User Manual & Datasheet V 2.1
7
Electrical Specifications
Please refer to Table 1 for Electrical Specifications.
PARAMETER
VALUE
Input Power Supply
18-30 V DC
Output
Open Collector - PNP Output (Load capacity upto 90 mA at
24 V DC)
Switching Indication
Red /Green LED ON/OFF
Switching Behavior
•
ON
•
OFF
Fail-safe Feature
Field selectable
•
Fail-safe High ( For Overflow Protection)
•
Fail-safe Low (For Dry Run Protection)
Power Consumption
Without Load
•
480 mW @ 24 V DC
•
168 mW @ 12 V DC
With Load
3W @ 24 V DC
Table 1: Electrical Specifications
8
Application Specifications
Please refer to Table 2 for Application Specifications.
PARAMETER
VALUE
Response Time
•
Covered
•
Uncovered
Value
•
0.5 second
•
1 second
Repeatability
±
0.5mm
Switching Hysteresis*
3mm
±
0.5mm
Fork Resonance Frequency*
1500Hz approx.
Minimum Liquid Density
0.7gm/cc
Maximum Viscosity of Liquid
10,000 cp
Solid Content Diameter
<
5mm
Temperature
•
Ambient
•
Process
Value
•
0
◦
C to
60
◦
C
•
0
◦
C to
150
◦
C
Table 2: Application Specifications
*
The reported values have been found with water as application medium, at room temperature.
Sapcon Instruments Pvt.Ltd.
R
6