Be sure to use a manifold valve for
air purging. If it is not available, use
a stop valve (field supply) for this
purpose. The “Hi” knob of the mani-
fold valve must always be kept closed.
Insulated tubes
Drain hose
Clamp
Hi
Lo
I
n
door
un
it
O
u
tdoor
un
it
Ma
n
ifold valve
(Excl
us
ively for R410A)
Pre
ssu
re
g
a
ug
e
Vac
uu
m p
u
mp
Char
g
i
ng
ho
s
e
(Excl
us
ively for R410A)
Vac
uu
m p
u
mp adapter
(Excl
us
ively for R410A)
(with rever
s
e flow preve
n
tio
n
)
17
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with
armoring tape. The drain hose may also be included
and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As
you wrap the tubing, overlap half of each previous tape
turn. (Fig. 25)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 47" (120 cm).
Do not wind the armoring tape too tightly, since this will
decrease the heat insulation effect. Also, be sure the con-
densation drain hose splits away from the bundle and drips
clear of the unit and the tubing.
5-7. Finishing the Installation
After finishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent rain
and draft from entering. (Fig. 26)
NOTE
5-6. Taping the Tubes
Fig. 25
6. Air Purging
Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they must
be purged completely.
G
pressure in the system rises
G
operating current rises
G
cooling (or heating) efficiency drops
G
moisture in the air may freeze and block capillary tubing
G
water may lead to corrosion of parts in the refrigerant system
I
Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been proper-
ly connected and all wiring for the test run has been
completed. Note that both narrow and wide tube service
valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove the
valve caps from the service valve on both narrow and
wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube
service valve. (Fig. 27)
CAUTION
CAUTION
The service port on the wide tube service valve
uses a Schrader core valve to access the
refrigerant system. The valve core is similar to
those used in automobile tires. Therefore, be
sure to use a vacuum hose connector which
has a push-pin inside.
Fig. 27
Fig. 26
Apply p
u
tty here
T
u
bi
ng
08-193 XHS1271 9/12/08 2:58 PM Page 17