background image

18

S4359128

6. Electrical Wiring

6-1. General Precautions on Wiring

(1)

Before wiring, confirm the rated voltage of the unit

as shown on its nameplate, then carry out the

wiring closely following the wiring diagram.

(2)

Provide a power outlet to be used exclusively for

each unit, and a power supply disconnect and

circuit breaker for overcurrent protection should

be provided in the exclusive line.

(3)

To prevent possible hazards from insulation

failure, the unit must be grounded.

(4)

Each wiring connection must be done in accor-

dance with the wiring system diagram. Wrong

wiring may cause the unit to misoperate or

become damaged.

(5)

Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6)

Unauthorized changes in the internal wiring can

be very dangerous. The manufacturer will accept

no responsibility for any damage or misoperation

that occurs as a result of such unauthorized

changes.

(7)

Regulations on wire diameters differ from locality

to locality. For field wiring rules, please refer to

your LOCAL ELECTRICAL CODES (ex. National

Electric Code: ANSI/NFPA70) before beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8)

To prevent malfunction of the air conditioner

caused by electrical noise, care must be taken

when wiring as follows:

The inter-unit control wiring and the remote control

wiring (option) should be wired apart from the inter-

unit power wiring.

AWG #12

AWG #12

C1852, CL1852

75 ft.

65 ft.

15 A

20 A

AWG #12

Models

6-2. Recommended Wire Length and Wire Diameter for Power Supply System

Time Delay
Fuse or
Circuit
Capacity

(B)

*1

 Inter-unit

Wiring

(A)

*1

 Power Supply

*1 Refer to the Wiring System Diagrams (See Fig. 6-3) for the meaning of “A”, “B”.

AWG = American Wire Gauge

Max. Wire
Diameter

Power Supply Terminal Base
(Outdoor Unit)

Capacity

6-3. Wiring Instructions for the Outdoor Unit

(1)

To take off the access panel, remove the 4

screws. (See Fig. 6-1)

(2)

Dismount plugs on the conduit plate.

(3)

Temporarily mount the conduits on the conduit

plate.

(4)

Properly connect both the power supply and inter-

unit lines to the corresponding terminals on the

terminal block.

Refer to the wiring diagram in Fig. 6-2 (which also

appears on the access panel).

Lock nut

Terminal
block

Access panel

Power supply

Inter-unit line

Plug

Conduit
plate

1822_M_I

Fig. 6-1

Summary of Contents for C1852

Page 1: ...ons for 2 Units or 2 Groups of Units 6 ELECTRICAL WIRING 18 6 1 General Precautions on Wiring 6 2 Recommended Wire Length and Wire Diameter for Power Supply System 6 3 Wiring Instructions for the Outdoor Unit 6 4 Examples of Incorrect Wiring 6 5 How to Connect Wiring to the Terminal CONTENTS Model Combinations Combine indoor and outdoor units only as listed below Indoor units Outdoor units XS1852 ...

Page 2: ...s Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced IMPORTANT Please Read Before Starting This air conditioning system meets strict safety and operating standards As the installer or service person it is an important part of your job to install or service the system so it operates safely and efficiently For ...

Page 3: ... 71 F WB 115 F DB Minimum 67 F DB 57 F WB 67 F DB 0 F DB CL Models Wireless remote control unit Part Name Figure Q ty 1 2 1 1 AAA alkaline battery Tapping screw Tapping screw Special screw 4 16 mm TOTA 4 16 1 General This booklet briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all a...

Page 4: ...of elevation difference between the 2 units Models C1852 Tubing Data CL1852 Tubing size Narrow tube in mm 1 4 6 35 Thickness 0 0314 0 8 mm outer dia Wide tube in mm 5 8 15 88 Thickness 0 0394 1 0 mm Limit of tubing length ft 65 Outdoor unit is higher 23 than indoor unit ft Outdoor unit is lower 23 than indoor unit ft Max allowable tubing length at shipment ft 33 Required additional refrigerant 1 o...

Page 5: ...he unit occurs DO select an appropriate position from which every corner of the room can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 2 1 install the unit w...

Page 6: ...ortion of the outdoor unit or incomplete combustion may result Donotintroduceforeignmatter into the air intake outlet or exhaust Donotpokethemwith such objects as a stick provide a solid base level concrete pad concrete block 4 in 16 in 10 40 cm beams or equal a minimum of 4 in 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life...

Page 7: ...stall the Indoor Unit 3 1 Suspending the Indoor Unit This unit uses a drain pump Use a carpenter s level to check that the unit is level 3 2 Preparation for Suspending 1 Fix the suspension bolts securely in the ceiling using the method shown in the diagrams Figs 3 1 and 3 2 by attaching them to the ceiling support structure or by any other method that ensures that the unit will be securely and saf...

Page 8: ...on bolt must be appropri ate for a distance between the bottom of the bolt and the bottom of the ceiling of more than 2 3 8 in as shown in Fig 3 4 3 Thread the 2 hexagonal nuts and washers field supply onto the 4 suspension bolts as shown in Fig 3 5 Use 2 sets of nuts and washers upper and lower so that the unit will not fall off the suspen sion lugs 4 Remove the protective cardboard used to prote...

Page 9: ...mum of 10 in Do not raise it any higher than 10 in as this could result in water leaks Fig 3 9 Do not install the pipe with an upward gradient from the connection port It will cause the drain water to flow backwards and leak when the unit is stopped Fig 3 10 Do not apply force to the piping on the unit side when connecting the drain pipe The pipe should not be allowed to hang unsupported from its ...

Page 10: ...er into the drain pan to check drainage 2 Do Test Run to check the drainage after complet ing installation When performing Test Run be sure to observe the Test Run procedure Refer to page 37 Be careful since the fan will start turning when checking the drainage 3 After drain checking is finished return the Operation Selector switch to the RUN position ON position and remount the tube cover To moun...

Page 11: ...ve the air intake grille and air filter from the ceiling panel Figs 3 13 and 3 14 a Remove the 2 screws on the latch of the air intake grille Fig 3 13 b Press on the 2 latches of the air intake grille with your thumb in the direction of the arrow to open the grille Fig 3 13 c With the air intake grille open about 45 remove the safety string hook on the grille side Fig 3 14 d Pull the air intake gr...

Page 12: ...mounting screws 3 7 Installing the Ceiling Panel 1 Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit The ceiling panel must be mounted in the correct direction Note that the 2 catches of the panel differ in size Confirm that the catches are correctly matched be tween the ceiling panel and the indoor unit body 2 Next check to see that the ceiling...

Page 13: ...ormance filter is used Screw 4 Air intake filter M5 L125 for fastening Screw 4 4 Duct connection flange box M4 L12 for fastening Duct connection box 1 for fresh air Duct connection flange 1 for connecting fresh air duct Do not connect the acces sory cord with socket to the electrical component box when the unit is used to take fresh air Do not connect the acces sory cord with socket when assemblin...

Page 14: ...3P plug of the indoor unit electrical component box Connect the 6P socket to the 6P plug from the operation selector Reattach the socket cover f INSTALLING THE HIGH PERFORMANCE FILTER OR SUPER LONG LIFE FILTER Fig 3 18 Turn the filter hooks of the air intake chamber Install high performance or super long life filter into the chamber Install in the correct direction Set the filter so that the arrow...

Page 15: ...correct operation use a screwdriver to screw the supplied special mounting screw into the wall Fig 4 1 d Hang the remote control unit from the mounting screw 2 Non removable mounting a Momentarily hold the remote control unit in the desired mounting position b Confirm that the air conditioner responds correctly when you press keys on the remote control from that position c After confirming correct...

Page 16: ...r pointed object to remove the plastic bushing which is inserted in the rear of the remote control unit The bushing can be discarded Fig 4 4 2 Align the cord with the groove of the remote control unit 3 Attach the mounting plate to the wall with the 2 supplied screws Then align the rail on the rear of the control unit with the slot of the mounting plate and slide the unit down as far as it will go...

Page 17: ...r up to 2 units or 2 groups of indoor units installed in the same room Two remote control units are necessary to allow the respective units or group to be controlled indepen dently An indoor unit cannot be controlled if its remote control unit is too far away more than 26 ft If the remote control unit does not work correctly bring it closer to the unit being operated and try again There should be ...

Page 18: ... ex National Electric Code ANSI NFPA70 before beginning You must ensure that installation complies with all relevant rules and regulations 8 To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as follows The inter unit control wiring and the remote control wiring option should be wired apart from the inter unit power wiring AWG 12 AWG 12 C1852 CL...

Page 19: ...it draws its power from the outdoor unit CAUTION 6 4 Examples of Incorrect Wiring The following are examples of improper wiring that result in system misoperation You should confirm that you have wired the units correctly before beginning the test run Problem 1 Short circuit will occur after approx 3 minutes and the power circuit fuse blows Problem 2 Air conditioner will not operate 1 2 3 G G 1 2 ...

Page 20: ...orm a loop suitable for the terminal screw 4 Shape the wire loop properly position it on the terminal plate and fix it securely with the terminal screw using a screwdriver For stranded wiring 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to expose the stranded wiring about 3 8 in Fig 6 4 2 Using a Pillips head screwdriver remove the terminal screw s on the ...

Page 21: ...he copper tube 4 Make a flare at the end of copper tube with a flare tool Fig 7 3 Use RIGID or equivalent A good flare should have the following characteristics inside surface is glossy and smooth edge is smooth tapered sides are of uniform length 7 3 Precaution before Connecting Tubes Tightly 1 Apply a sealing cap or water proof tape to pre vent dust or water from entering the tubes before they a...

Page 22: ...r and Outdoor Units 1 Tightly connect the indoor side refrigerant tubing with the outdoor side tubing Fig 7 6 2 To fasten the flare nuts apply specified torque as Table 7 1 Tightening Torque Approx 140 180 kg cm 120 160 Ibs in Approx 680 820 kg cm 590 710 lbs in Tube Dia 1 4 6 35 mm 5 8 15 88 mm 7 6 Insulating the Refrigerant Tubing Always insulate tubes after completing leak tests on all connecti...

Page 23: ...e armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall As you wrap the tubing overlap half of each previous tape turn Fig 7 9 3 Clamp the tubing bundle to the wall using 1 clamp about every 3 feet Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also ensure that the condensation drain hose splits away from ...

Page 24: ...ice valve on both narrow and wide tubes 3 Connect a vacuum pump and a manifold valve with pressure gauges to the service port on the wide tube service valve Fig 8 1 Be sure to use a manifold valve for air purging If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept closed 4 With the Lo knob of the manifold valve open run the vacuum pump The...

Page 25: ...Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure Then remove the hose 11 Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench or box wrench Next mount the valve cap and tighten it with a torque wrench the cap needs to be tightened with the torque of 170 ibs in 200 kg c...

Page 26: ...ontrol unit to confirm remote control unit operation Set the Operation Selector at the ON position Other wise the unit will stop or will not run correctly Operation selector Air filter Air intake grille 1323_M_I TEST OFF ON Fig 9 1 Fig 9 2 Service TEST RUN switch RUN TEST RUN Bottom Remote control unit viewed from rear 0543_M_I CAUTION Important 9 2 Performing Test Run with Optional Wired Remote C...

Page 27: ...o close the service valve Be sure to confirm that the wide tube service valve is fully open 3 Press the operation button and start cooling operation 4 When the low pressure gauge reading falls to 1 to 0 5 kg cm2 14 2 to 7 1 PSI fully close the wide tube valve stem with a standard screwdriver Then quickly stop the unit 5 Disconnect all gauges and hose and replace the bonnets and the valve caps as t...

Reviews: