W-2WAY ECO-i SYSTEM
Remote Controller Functions
4
- 6
2. Detailed Settings Function
4
Item code
Item
Setting data
No.
Description
(1B)
Forced thermostat ON time
0000
5 minutes
0001
4 minutes
Cooling discharge
temperature shift
–010
–10°C
–009
–9°C
–008
–8°C
0010
10°C
Heating discharge
temperature shift
–010
–10°C
–009
–9°C
–008
–8°C
0010
10°C
Temperature shift for
cooling/heating change in
auto heat/cool mode
0001
±1°C
0002
±2°C
0003
±3°C
0007
±7°C
(Upper limit)
Change to remote
control temperature
setting range
Cooling
0018
18°C (Lower limit at shipment)
0019
19°C
(Lower limit)
0029
29°C
0030
30°C (Upper limit at shipment)
(Upper limit)
Heating
0016
16°C (Lower limit at shipment)
0017
17°C
(Lower limit)
0029
29°C
0030
30°C (Upper limit at shipment)
(Upper limit)
Dr
ying
0018
18°C (Lower limit at shipment)
0019
19°C
(Lower limit)
0029
29°C
0030
30°C (Upper limit at shipment)
(Upper limit)
A
uto heat/cool
0017
17°C (Lower limit at shipment)
0018
18°C
(Lower limit)
0026
26°C
0027
27°C (Upper limit at shipment)
Humidifi er operation
0000
Normal
0001
Ignore heat exchanger temperature conditions.
Filter (CN70) input
switching
0000
Filter input (differential pressure switch input)
0001
Alarm input (for trouble input about air cleaner or similar device)
0002
Humidifi er input (Operates linked with drain pump when humidifi er is
ON.)
Indoor unit electronic
control valve
0000
Present (Setting at shipment)
0002
None
T10 terminal switching
0000
Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001
Used for OFF reminder
0002
Fire prevention input