−
42
−
Appendix. Usage notes for SANUPS SOFTWARE STANDALONE
When using supplied “SANUPS SOFTWARE STANDALONE”, please note the following
instructions.
“Charge” on the main screen of “SANUPS SOFTWARE STANDALONE”
For the charge rate (as a %) of the battery displayed on the main screen of “SANUPS
SOFTWARE STANDALONE”, please note the followings.
Refer to §6.1 “Main Screen” in the User Guide of SANUPS SOFTWARE STANDALONE for
details.
1. Proceed as follows to charge the batteries of the UPS for 12 hours or more at initial startup
of the UPS.
(
Use the internal battery only.
)
Perform this operation before powering the connected load devices on.
①
Verify that the battery connector is connected correctly.
See §6.4 “Preparation Before Installation” in the E11A Instruction Manual for details.
②
Perform step Ҥ9.1
①
” in the E11A Instruction Manual.
③
Verify that the Green INPUT LED on the UPS control panel lights.
Charging starts automatically.
④
Keep the UPS in the condition of step
③
for 12 hours or more.
However, you use the Battery Modules (Option), in the following list.
Battery Modules
Charge time
BC-E11A202US
×
1unit
36 hours or more
BC-E11A202US
×
2 unit
60 hours or more
BC-E11A202US
×
3 unit
84 hours or more
BC-E11A202USL
×
1 unit
48 hours or more
BC-E11A202USL
×
2 unit
84 hours or more
2. If the UPS is stopped and then restarted, even when the UPS is charged by step 1,
“Charge” might be displayed as “80%” or “90%” not “100%” on the main screen.
This occurs owing to the operating conditions such as ambient temperature.
However after normal operation of the UPS for 1 or 2 hours, “Charge” is displayed properly.
But if you use the Battery Modules (Option), after normal operation of the UPS for 2 hours
or more, “Charge” is displayed properly.
3. Connect the battery connector correctly. If the UPS is operated without the batteries,
“Charge” is not displayed properly. Moreover, even if the battery connector is reconnected
and operates the UPS, the proper charge rate is not displayed immediately.
After normal operation of the UPS for 12 hours or more, “Charge” is displayed properly.
4. Display of “Charge” is only an approximation. An actual charge rate of the battery might be
different.
“Backup Time” on the main screen of “SANUPS SOFTWARE STANDALONE”
For the presumed “Backup Time” (in minutes) displayed on the main screen of “SANUPS
SOFTWARE STANDALONE”, please note the followings.
Refer to §6.1 “Main Screen” in the User Guide of SANUPS SOFTWARE STANDALONE for
details.