− 14 −
Each press of the button switches the displayed information as follows.
(1) Results at the completion of measurement :
(A) Time of completion of measurement.
(B) Value at completion of measurement.
(C) DAR or PI value.
(2) Results at 15 or 30 seconds after the start of measurement :
(A) 15 or 30 seconds.
(B) Value at 15 or 30 seconds after the start.
(C) DAR value.
(3) Results at 1 minute after the start of measurement :
(A) 1 minute.
(B) Value at 1 minute after the start.
(C) DAR value.
(4) Results at 10 minutes after the start of measurement:
(A) 10 minutes.
(B) Value at 10 minutes after the start.
(C) PI value.
(5) Returned to display (1).
* If the measurement time is insufficient, display (1) is returned by
skipping other information.
5-6 Voltage Characteristics at Measuring Terminals
MG5000 Output characteristics
Output voltage
(
V
)
Insulation resistance
5000V range
6000
0.1
M
Ω
1
M
Ω
10
M
Ω
100
M
Ω
1000
M
Ω
10
G
Ω
100
G
Ω
1000
G
Ω
5000
4000
3000
2000
1000
0
2500V range
1000V range
500V range
250V range
* The batteries consume rapidly in measurement of resistance lower
than rated test voltage/3 mA for a long period. It is recommended
to measure low resistances quickly in a short period.
(5000 V/1.8 MΩ, 2500 V/0.9 MΩ, 1000 V/0.36 MΩ. 500 V/0.18 MΩ,
250 V/0.0 9MΩ)