GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
99/
150
5.3.2. List of Programmable Parameters P500 to P523
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P500
DC-Bus Voltage Reference
BASIC
609
Depending
on voltage
class
P510
Proportional Term of DC-bus Voltage Regulator
for Min. Error
ENGINEERING
620
Depending
on size and
voltage
class
P511
Integral Term of DC-bus Voltage Regulator for
Min. Error
ENGINEERING
621
P512
Proportional Term of DC-bus Voltage Regulator
for Max. Error
ENGINEERING
622
P513
Integral Term of DC-bus Voltage Regulator for
Max. Error
ENGINEERING
623
P514
Min. Error Threshold
ENGINEERING
624
2.000%
P515
Max. Error Threshold
ENGINEERING
625
14.000%
P516
Regenerative Inductance
ENGINEERING
626
Depending
on size and
voltage
class
P520
DC-Bus Current Limit
ENGINEERING
630
100.00%
P521
Proportional Term of DC-Bus Current Regulator ENGINEERING
631
Depending
on size
P522
Integral Term of DC-Bus Current Regulator
ENGINEERING
632
P523
Power factor Adjustment
ENGINEERING
633
0
Table 14: List of parameters P500 to P523
P500 DC-Bus Voltage Setpoint
P500
Range
Class 2T
360
400
Class 4T
700
780
Class 5T
900
950
Class 6T
1000
1130
Class 2T
360
400 V
Class 4T
700
780 V
Class 5T
900
950 V
Class 6T
1000
1130 V
Default
Class 2T
380
Class 4T
700
Class 5T
950
Class 6T
1050
Class 2T
380 V
Class 4T
700 V
Class 5T
950 V
Class 6T
1050 V
Level
BASIC
Address
609
Function
This parameter defines the setpoint of the DC-bus voltage.