GUIDE TO THE
REGENERATIVE APPLICATION
SINUS PENTA
113/
150
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P570
Instantaneous Undervoltage Alarm
Enable
ENGINEERING
690
1: On
P571
Min. Voltage Alarm Enable
ENGINEERING
691
1: On
P572
Max. Voltage Alarm Enable
ENGINEERING
692
1: On
P573
RMS Alarm Enable
ENGINEERING
693
1: On
P574
Frequency Alarm Enable
ENGINEERING
694
1: On
P575
Instantaneous Overvoltage Alarm
Enable
ENGINEERING
695
1: On
Table 19: List of parameters P550 to P575
NOTE
(*)
The User Level and the value of the parameters above depend on
P576
.
The values given in the table above are set when
P576
= 0: No Default (i.e. no
regulations selected).
P576 Default Mains Settings
P576
Range
0
3
0
No Default
1
UL 1741
2
IEEE 1547
3
CSA C22.2
Default
0
0
No Default
Level
ENGINEERING
Address
281
Function
If this parameter is set to a value >0, the following parameters will be
affected by the selected regulations:
P550
,
P552
,
P554
,
P556
,
P558
,
P560
,
P562
,
P564
,
P566
,
P568
,
P558a
,
P560a
.
Parameter
P576
may be changed either within 12 hours from the latest
modification or after executing command
I500
. Afterwards, the setting in
P576
becomes permanent.
I500 Default Lock Command
I500
Range
0
1
0
NO COMMAND
1
LOCK
Default
This is not a parameter: it is set to zero every time the equipment is
powered on and every time the command is executed.
Level
ENGINEERING
Address
283
Function
0
Inactive
1
Parameter
P576
is not modifiable (only if >0) over the time span of
12 hours. This is a permanent operation.