SINUS PENTA
GUIDE TO THE
REGENERATIVE APPLICATION
106/
150
5.4.2. List of Programmable Parameters P530 to P542 and I003
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT VALUES
P530
Number of Half-line Cycles
ENGINEERING
956
10 T/2
P531a/b/c
Phase R/S/T Voltage RMS Gain
ENGINEERING
958/959/960
0
P532a/b/c
Phase R/S/T Current RMS Gain
ENGINEERING
961/962/963
0
P533a/b/c
Phase R/S/T Active Power Gain
ENGINEERING
964/965/966
0
P534a/b/c
Phase R/S/T Reactive Power
Gain
ENGINEERING
967/968/969
0
P535a/b/c
Phase R/S/T Voltage RMS Offset
ENGINEERING
970/971/972
0
P536a/b/c
Phase R/S/T Current RMS Offset
ENGINEERING
973/974/975
0
P537a/b/c
Phase R/S/T Active Power Offset
ENGINEERING
976/977/978
0
P538a/b/c
Phase R/S/T Reactive Power
Offset
ENGINEERING
979/980/981
0
P539a/b/c
Phase R/S/T Phase Calibration
ENGINEERING
982/983/984
0
P540
NoLoad Threshold
ENGINEERING
953
0:Disable
P542
CT Coil Ratio for ADE
ENGINEERING
992
See Table 5 and
I003
Energy Counter Reset
ENGINEERING
1390
Inactive
Table 17: List of parameters P530 to P542 and I003
P530 Number of Half-line Cycles
P530
Range
0
65535
0
65535 T/2
Default
10
10 T/2
Level
ENGINEERING
Address
956
Function
This parameter sets the number of half-line cycles for the accumulation of
the active energy and the reactive energy in the respective counters.
Example: when frequency is 50Hz, T=20ms and T/2=10ms; if
P530
=100
T/2, energy is accumulated every 100x10=1s.
If
P530
is set to high values, the calculation of energy accumulation is
slower but accurate; on the other hand, if
P530
is set to low values, the
calculation of energy accumulation is faster but less accurate.
As a general rule, set short times when high power ratings are required,
and set longer times when low power ratings are required.
CAUTION
When the number of half-line cycles is set too high, overflow can occur,
especially
in case of high power ratings, thus turning “plus” into “minus”
and vice versa.