PROGRAMMING GUIDE
SINUS PENTA
341/486
C172 KEYPAD LOCK Input
C172
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1172
Function
This function
avoids accessing parameter modification
through the removable
display/keypad and
avoids accessing the LOCAL mode
by pressing the
LOC/REM
key
or by enabling the
LOCAL
input function
(C181).
NOTE
If the
LOCAL
mode is already active, the
LOCK
command will have no effect on the
LOCAL
function: it only avoids changing the programming parameters, while it is still
possible to send references and the
START/STOP/REV/JOG/RESET
commands
via
keypad
.
If the
LOCK
command is active and the
LOCAL mode
is disabled, the
LOCK
function
prevents the LOCAL mode from activating.
C173, C174 MOTOR SEL Input
C173
C174
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ENGINEERING
Address
1173, 1174
Function
This function
activates motor
2 and 3
and sets the relevant programming parameters
(see Table 104).
A different active motor can be selected only when the drive is disabled.
Table 104: Motor selection
Value of the terminal allocated to the
Sel. Motor
n.2
(
C173
) function
Value of the terminal allocated to the
Sel.
Motor n.3
(
C174
) function
Active motor
0
0
Motor n.1
1
0
Motor n.2
0
1
Motor n.3
1
1
Motor n.1
NOTE
When both inputs are enabled, Motor 1 is selected again.