Santa Fe Ceiling HEPA Installation & Operation Instructions
• Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction.
• When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
Location of the Santa Fe Ceiling HEPA
• The Santa Fe Ceiling HEPA fan boxes must be installed 4’ to 12’ from the Santa Fe Ceiling HEPA filter
box. The boxes are to be connected with 10” insulated flexible ducting. The fan box should be connected
with as straight duct path as possible. Sharp bends and collapsed ducting will affect system performance.
• The Santa Fe Ceiling HEPA system is ducted above drop ceilings or open ceiling installations. The
filter box return and supply diffuser(s) should be positioned approximately 20’ apart, with the fan box
positioned in the middle of the duct return. The supply ducts should be located to provide balanced
coverage no more than 15’ from the fan box.
SAFETY PRECAUTIONS
CAUTION!
CAUTION!
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING
Hanger tabs for
3/8” threaded rod
(4 supplied)
10” Outlet
10” Outlet
11.7”
19”
Electrical
Box Cover
10”
Inlet
Standard: 2 Fan Box
11.7”
Mini: 1 Fan Box
10” Outlet
Electrical
Box Cover
10”
Inlet
Hanger tabs for
3/8” threaded rod
(4 supplied)
11”
14”
INSTALLATION INSTRUCTIONS
SYSTEM COMPONENTS
1. Custom return filter enclosure with 10” collar
2. Gasketed HEPA filter: 18” x 18” x 2.5
3. MERV-8 pre-filter: 20” x 20” x 1”
4. 25’ of 10” R6 insulated ductwork (not included)
5. Supply air diffusers with 10” collar (not included)
6. Fan box with 6’ cord
2
3
1
5
6
5
4
4