Santa Fe Rx Installation & Operation Instructions

www.Santa-Fe-Products.com | 1-800-533-7533

Service - Troubleshooting

 CAUTION!

TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.

  Symptom 

Possible Reason 

Troubleshooting Procedure

 

Troubleshooting Procedure for Performance  

Related Issues
This method of diagnosis is used to function 
check the internal components in the dehumidifier. 
This is to be used when a performance issue is 
suspected.
1.  Set the humidity controller all the way to the 

most humid setting or off position – Did the 
unit shut off?

2.  If yes, turn the fan setting to the ON position – 

does the fan start?

3.  If fan starts, leave in the fan ON position and 

set the humidity all the way to driest setting. 
May have to wait 5 minutes for the compressor 
to start.

4.  Listen for a distinct buzzing/humming sound 

of a compressor starting up – do you hear this 
noise?

5.  If compressor is running and continues to run, 

after about 15 minutes you should feel a slight 
increase in air temperature being discharged 
out of the discharge air side of the unit.

6.  If so, depending on your environmental  

conditions (temp/Rh%), you should see some 
water production out of the hose within  
30 minutes or so. (

Note: If the room  

temperature is 55 degrees or below and/or  

in area of low relative humidity, the  

dehumidifier will produce little to no water.)

7.  Collecting the water removed in a 24 hour period 

will give a measurement of performance. 

 WARNING!

 

ELECTRICAL SHOCK HAZARD:

  

ELECTRICAL POWER MUST BE PRESENT 

TO PERFORM SOME TESTS. THESE TESTS 

SHOULD BE PERFORMED BY A QUALIFIED 

SERVICE PERSON.

Fan is not running. 
Dehumidification  
or fan is being 
called for.

1.  Loose connection in  

fan circuit.

2.  Obstruction prevents 

fan impeller rotation.

3. Defective fan.
4. Defective fan relay.

Low dehumidification 
capacity (evaporator 
is frosted  
continuously).  
Dehumidification is 
being called for.

1.  Defrost thermostat loose 

or defective.

2. Low refrigerant charge.
3.  Dirty air filter(s) or air flow 

restricted.

4.  Excessively restrictive 

ducting connected to unit.

Dehumidifier  
removes some  
water, but not as 
much as expected. 

1.  Air temperature and/or  

humidity have dropped. 

2.  Humidity meter and or 

thermometer used are  
out of calibration.

3.  Unit has entered defrost 

cycle. 

4.  Dirty air filter(s) or air flow 

is restriced. 

5.  Defective defrost  

thermostat. 

6. Low refrigerant charge. 
7.  Air leak such as loose 

cover or ducting leaks. 

8. Defective compressor. 
9. Restrictive ducting. 

Summary of Contents for 4030440

Page 1: ...ta Fe Rx is a great solution for a living room bedroom office space or anywhere that needs supplemental dehumidification Its clean design blends into any home or office d cor P N 4030440 Serial No Ins...

Page 2: ...s 4 Dehumidifier Set Up 5 Items Included In Box 5 Important Precautions 5 Location Considerations 5 Drain Installation 6 Operation 7 Humidity Control Adjustment 7 Fan Operation 7 Defrost Cycle 7 Air F...

Page 3: ...unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is designed to be installed indoors only No user se...

Page 4: ...r MERV 11 Standard Pleat Size 16 x 20 x 2 Power Cord 10 115 VAC Ground Drain Hose 3 16 ID x 20 15 Lift Capacity Internal pump included Refrigerant Type R410A Refer to manufacturers label for more info...

Page 5: ...se coming from under its base The hose about the diameter of a TV coaxial cable must be routed to a drain or outside It can pump condensate 15 above the unit and can be extended Install the unit with...

Page 6: ...greater to avoid overloading the pump Be sure the extension is at a down word slope to the drain Larger diameter hose is available from the factory or may be purchased from many hardware stores If the...

Page 7: ...duce it to 45 50 RH A humidity meter is supplied upon return of the survey warranty registration card a meter is recommended to accurately monitor humidity levels Additional meters are available for p...

Page 8: ...WEAR OR UNIT DAMAGE Front View TOP Front View FILTER TOP TOP FILTER Changing the Optional Filters An optional filter housing is available that attaches to the back of the machine and adds 6 1 2 to the...

Page 9: ...9 1 800 533 7533 www Santa Fe Products com Santa Fe Rx Installation Operation Instructions MERV Rating Chart Air Filtration http www mechreps com PDF Merv_Rating_Chart pdf...

Page 10: ...pacity If used in an area that may become wet a GFCI protected circuit is recommended The unit should not be used in areas prone to flooding Consult local electrical codes for any further information...

Page 11: ...frigerant type Compressor Capacitor Replacement This compressor is equipped with a two terminal external overload and a run capacitor but no start capacitor or relay WARNING SERVICING THE SANTA FE RX...

Page 12: ...temp Rh you should see some water production out of the hose within 30 minutes or so Note If the room temperature is 55 degrees or below and or in area of low relative humidity the dehumidifier will p...

Page 13: ...s not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Cus...

Page 14: ...14 Santa Fe Rx Installation Operation Instructions www Santa Fe Products com 1 800 533 7533...

Page 15: ...15 1 800 533 7533 www Santa Fe Products com Santa Fe Rx Installation Operation Instructions...

Page 16: ...www Santa Fe Products com 1 800 533 7533...

Reviews: