VI. Installation and debugging

Determine the location, mounting distance and numbers for mounting the detectors in the protection area
according to relevant provisions and regulations of the local codes.
A self-contained complete base is necessary during the installation of a detector. As shown in Fig.6, the
model, the external dimensions, the mounting hole diameter and the mounting hole spacing of the base
are DZ-912, 100mm

×

26.4mm (diameter

×

thickness), 4.5mm and 44.5mm

64.3mm respectively.

Fig.6(unit:mm)

Wiring requirement:

It is proper to use RVS twisted pairs with a section area of equal to or larger than 1.0mm

2

for the signal

buses L1 and L2.

Specific installation and debugging methods:

1.

Make sure the type of the detector matches the type of the host machine of the fire alarm
control panel;

2.

Use two M4 screws to fix the matched mounting base on the designated position via the
mounting holes A and B shown in Fig.6 as instructed in the construction drawing and make sure
the matched mounting base has been firmly installed.

3.

Use a coder to make the detector coded according to the detector address on the construction
drawing.

4.

Disconnect the power supply of the fire alarm control panel and connect the detector correctly
according to the construction drawing.

5.

The lower edge of the detector base raised position aligned with the groove position, and then
the detector into the base, the detector clockwise until it locks into place the detector.

6.

After all the products are installed and checked, connect the power supply of the fire alarm
control panel and conduct automatic login.

7.

when automatic login is success, the red indicator of the detector will blink once about every 12
seconds, which suggests that the detector has begun to operate normally.

8.

Finally conduct an alarm test for the detector through some special tools or direct hot air gun

- 4 -

blowing. After the detector gives a fire alarm, the indicator will remain lit and the fire alarm
control panel will simultaneously give corresponding alarm prompt information. After the alarm
test, reset the fire alarm control panel and restore to the monitoring status.

VII. Precautions

1.

A detector can not share an address with other equipment in a single bus circuit, or else an

address conflict may occur.

2.

Never dismount the protective cover delivered with the detector too early after the field

installation and before the use of the detector, or else the detector may be contaminated.

3.

It is not permitted to use open flames (such as lighters) to firing thermistor during alarm tests,

so as to avoid damage to the detector. It is recommended to use a hot air gun and other heating

equipment in a simulation alarm test.

4.

The protection area and quantity of the detectors should comply with relevant provisions and

regulations of the local codes

VIII. Maintenance

Warning: Before conducting maintenance for a detector, inform the related management

department that the monitoring will be stopped temporarily when the system maintenance.

Meanwhile, disable the logic control function of the area or system to be maintained to avoid

unnecessary alarm linkage. After the test, inform the management department to restore the

normal functions of the system.

1.

According to the requirements of local codes, each quarter, some special testing instruments should

be used to test the detector

s operation and confirm the indication state of its indicators by batch

and stage; for a detector that has been installed and used, It is recommended to have it maintained

once every two years.

2.

If a detector fails due to a material defect or a manufacturing process defect under normal

conditions of use in one year following the date of its delivery, we shall repair or replace it for free.

However, the faults of the detector due to artificial damage, improper use, or authorized adjustment,

reconstruction or disassembly are not covered in the guarantee and we shall assume no

responsibilities for any the consequence thereby caused.

3.

We may provide paid repair service for products with any faults beyond the guarantee range. If you

have such products that need repair, please contact us. When sending such a product to us for

repair, you are expected to provide some important information about the product, such as the

phenomenon and possible cause of the product fault, so that we can find out the cause of the fault

in the shortest time and so the information may be used as a reference in our future product

development and improvement.

IX. Fault analysis and troubleshooting

Fault

Possible cause

Troubleshooting method

Remarks

The detector can

t be

coded.

The internal circuit is damaged.

Send the detector back to the factory for

repair.

The detector can

t be

logged into normally.

The detector has no address or

has a coincident code.

Recode the detector.

The detector reports a

fault after login.

The contact with the base is poor

Inspect and reinstall the base.

The internal circuit is damaged.

Send the detector back to the factory for

repair.

The detector reports a

fire alarm after login.

The internal circuit has failed.

Send the detector back to the factory for

repair.

The

detector

can

t

send out fire alarm

signal during an alarm

test.

The internal circuit is damaged.

Send the detector back to the factory for

repair.