background image

 

5. 

Usage:  Do  not  connect  the  power  supply  until  the  address  of  the  horn/strobe  has  been  set  and 
confirmed  and  the  fire  alarm  control  panel  has  been  properly  connected.  After  the  fire  alarm control 
panel  is  successfully  reset, the  red  status  indicator  (see  Fig.3  for  its  location)  of  the  horn/strobe  will 
blink.  After  the  horn/strobe  receives  an  operation  signal,  the  status  indicator  will  remain  lit  and  the 
horn/strobe will give both horn/strobe alarm signals. After the system is muted or reset, the horn/strobe 
will stop outputting horn/strobe alarm signals and the status indicator will start to blink again. 

VI. Installation and debugging 

A  special  base  is  necessary  during  the  installation  of  a  horn/strobe.  As  shown  in  Fig.4,  the  external 
dimensions  of  the  special  base  are  142

×

84

×

10mm (L

×

B

×

H).  The  horn/strobe  is  subject  to  a  four-wire 

non-polarity connection: Terminals 1 and 2 are respectively connected with the ter24V and GND 
of the DC power supply terminals 3 and 4 are respectively connected with the terminals L1 and L2 of the 
signal bus of the fire alarm control panel. See Fig.5.

 

 

Fig.4                                                                            Fig.5 

Specific installation and debugging methods: 

1. 

Use two M4 screws to  fix  the matched  mounting  base on the  designated  position  via the mounting  holes 
shown in Fig.4 (the installation may be done horizontally or vertically. Choose any two of the six mounting 
holes for installation) as instructed in the construction drawing and make sure the matched mounting base 
has been firmly installed. 

2. 

Disconnect the power supply of the fire alarm control panel and connect all the bases correctly in the way 
shown in Fig.5, which is a construction drawing. 

Note: When there are a lot of horns/strobes in a system, it is necessary to consider the loading capacity of 
the  power  supply  of  the  fire  alarm  control  panel.  An  external  DC24V  auxiliary  power  supply  might  be 
necessary at this time. Please follow the construction design drawings.       

3. 

Make sure the type of the horn/strobe matches the type given on the construction drawings. Use a coder to 
code the horn/strobe according to the address code marked on the construction drawings. 

4. 

After  all  the  horns/strobes  are  installed  and  checked,  connect  the  power  supply  of the  fire  alarm  control 
panel and conduct automatic login. 

5. 

After a horn/strobe logs into the fire alarm control panel, the red status indicator of the horn/strobe will blink; 
after the horn/strobe receives an operation signal, the red status indicator will remain lit and the horn/strobe 
will  give  both  horn/strobe  alarm  signals.  After  the  system  is  muted  or  reset,  the  horn/strobe  will  stop 
outputting horn/strobe alarm signals and the status indicator will restore to the monitoring status and start to 
blink again. 

VII. Precautions   

1.  Pay attention to the marking and polarities of the terminals during installation and wiring. 
2.  Do  not  make  different  products  share  the  same  address  in  a  single  alarm  circuit  or  the  system  will  fail  to  operate 

normally. 

3.  Make  sure  during  installation  that  there  are  no  objects  in  front  of  the  horn/strobe  that  block  the  light  given  by  the 

horn/strobe and/or prevent the horn/strobe from sounding.   

4.  Make the installation comply with related provisions of the Code for Installation and Acceptance of Fire Alarm System 

(GB50166-2007). 

VIII. Maintenance and inspection 

1.  As specified in national standard Code for Installation and Acceptance of Fire Alarm System (GB50166-2007), at least 

quarterly tests should be done for each horn/strobe.   

2.  If a horn/strobe fails due to a material defect or a manufacturing process defect under the normal conditions of use in 

one year following the date of its delivery, we shall repair or replace it for free. However, the faults of the horn/strobe due 
to artificial damages, improper  use  or unauthorized adjustment, reconstruction  or  disassembly are not covered  in the 
guarantee and we shall assume no responsibility for all the consequences thereby caused. 

 

3.  We may provide a  paid repair service  for the  products with any  faults beyond the  guarantee range.  If you  have such 

products needing repair, please contact us. W hen sending such a product to us for repair, you are expected to provide 
some important information about the product, such as the phenomenon and possible cause of the product fault, so that 
we can find out the cause of the fault in the shortest time and the information may be used as a reference in our future 
product development and improvement. 

IX. Fault analysis and troubleshooting 

 

Fault phenomenon   

Possible cause   

Troubleshooting method 

Remarks 

The wiring is wrong. 

Inspect whether or not the wiring 
is correct. 

 

The  linkage  function  has  not 
yet been enabled. 

Inspect  whether  or  not  the 
general linkage indicator is lit. 

 

The  short-circuit  block  is  set 
wrong. 

Inspect  whether  or  not  the 
short-circuit block is correctly set 
and  whether  or  not its contact is 
good. 

 

The horn/strobe cannot 

give a horn/strobe alarm 

signal. 

The 

internal 

circuit 

is 

damaged. 

Send the horn/strobe back to the 
factory for repair. 

 

 

 

 
 
 
 
 

Reviews: