  Instruction Manual of SG-991E Fire Alarm Horn/Strobe   

------ Please read this Manual carefully before installing and using the product.    ----- 

I. Product overview

 

The SG-991E fire alarm horn/strobe (horn/strobe for short) is a kind of product manufactured by our company to be used with 
bus-type fire alarm control units. Controlled by a microprocessor, the horn/strobe can realize real-time communication with a 
bus-type fire alarm control unit and receive the control commands sent by it. W hen in a routing inspection, the red status 
indicator will blink; after an accident happens, the horn/strobe will start to operate after 
receiving a startup command from the bus-type fire alarm control unit. The red status 
indicator will remain lit and the horn/strobe will give a flashing signal and an audible 
alarm signal to notify the persons on the scene of the accident that a fire has occurred 
on the site and of the necessity to take related evacuation measures, thus preventing 
the fire accident from becoming a major one. The horn/strobe may be restored to the 
monitoring status after the MUTE or RESET key on the bus-type fire alarm control unit 
is pressed.   
The  horn/strobe  may  be  used  to  give  audible  alarms  and  flashing  alarms  on  the 
scenes of accidents. It is suitable for places like high-rise residential buildings, public 
places, hotels, amusement buildings, factories, shopping centers, hospitals, schools, 
office  buildings  and  stock  exchanges,  particularly  places  with  low  visibility  or  the 
possibility of generation of smoke. 

II. Product features

 

ü

 

It can realize complete electronic coding and in situ rewriting with the help of a 

coder. 

ü

 

The audible alarm and flashing alarm may be set freely. In other words, the horn/strobe may give an audible alarm 

and a flashing alarm at the same time or separately and it can be adapted to different working environments.   

ü

 

  Designed with an upper cover and a lower cover, it can be installed, debugged and maintained conveniently.   

ü

 

It uses multiple super bright red LEDs as light sources for visual display, ensuring a striking display, a longer service 

life and low power consumption. 

III. Technical parameters

 

1. 

Executive standard: GA385- 2002 

2. 

  Operating voltage: DC24V (pulse modulation) 

3. 

Operating current: quiescent current: 

1mA (the current consumed by the bus); alarm current: 

120mA@DC24V   

4. 

Operating environment: Temperature: 

10

+55

; relative humidity: 

95% (40

, without condensation)

 

5. 

Flushing rate: one time/s 

6. 

Alarm volume: 

85dB (measured at a place 3m in front of the horn/strobe) 

7. 

Coding method: Electronic coding 

8. 

Wiring method: Four-wire system, non-polarity two signal buses (L1, L2) and power lines (+24V, GND) 

9. 

Matched host machine: JB-QBL-MN/300E 

IV. Appearance and dimensions (see Fig.1)

 

     

Fig.1 

V. Use and engineering application   

Fig.2 is the schematic diagram of the rear cover of the horn/strobe. 

 

 
Fig.2 

 

2.  Selection  between  audible  alarm  and  flashing  alarm:  Select  through  the  jumper  (JP1)  below  the 

debugging port lid on the back of the horn/strobe, following the instructions of the jumper. 

 

Jumper setup   

Function   

 

Audible alarm and flashing alarm (factory 

default) 

 

Flashing alarm (no audible alarms will be 

given) 

 

Audible alarm (no flashing alarms will be 

given) 

    Warning: The output mode of a horn/strobe can be one of the three options in the table 

above only. 

3.  Fig.3 shows the general functions and wiring diagram of the product. 

 

Fig.3 

4.  Address coding: When a horn/strobe is coded, it is unnecessary to disassemble the wire connecting it 

with the host machine; online coding may be done. The specific method is as follows: Open the cover 
of the coding setup window, insert the output plug (a four-pin connector) of the coder into the address 
coding  socket  (the  socket  J2  in  Fig.2)  of  the  horn/strobe,  set  the  coder  with  the  coding  function, 
compile the correct address code and press the RUN key to complete the address coding. (Note: See 
the User

s Manual of the coder for detailed operation information.) 

  Warning: It is necessary to have 

online coding

 done when the system is powered off 

or related equipment may be damaged. 

Definitions of terminals: 

1---+24 power input terminal     
2---GND power ground 
3---Bus input terminal L1 
4---Bus input terminal L2 

Debugging port

 

Enlarged drawing

 

JP1:  Setup  of  selection  between 
audible alarm and flashing alarm

 

J2: Address coding socket

 

Connecting terminal

 