Instruction manual of QM-AN-965K Emergency Start/Abort Switch

------

Please read this manual carefully before installing and using the product

-----

I. General description

II. Technical parameters

1. Operating voltage: 24VDC (20VDC

28VDC)

2. Operating current:

30mA

3. Capacity of the output control contact: 2A@DC24V
4. Operating environment: Indoor, temperature:

10

℃~

+55

Relative humidity:

95% (

40

℃±

2

, without condensation)

III. Instructions

1. Installation dimension of the QM-AN-965K Emergency Start/Abort Switch

2. Schematic circuit diagram

3. Terminal description

QM-AN-965K

JB-QBL-QM300/4

JB-QBL-QM200

JB-QB-QM200/4

Leading-out

Terminal

No.

Terminal

function

Leading-in

Terminal No.

Of the zone

control

terminal

board

Terminal

function

Leading-in

Terminal No.

Of the main

control

board

Terminal

function

Leading-in

Terminal No.

Of the zone

control

board

Terminal

function

1

GND

1

AGND

GND

(Between 18

and 19)

AGND

32

AGND

2

24V

6

+24V

1

+24V

31

+24V

3

STOP/NO1

1

AGND

GND

AGND

6

AGND

4

STOP/NO2

2

STOP

19

Emergency stop

control signal

5

STPB

5

START/NC1

5

START

17

Emergency start

control signal

1

STRB

6

START/NC2

6

+24V

1

+24V

2

+24VK

IV. Precautious

1. The minimum 1.5mm

2

BV line is used to supply power; the minimum 1.0mm

2

RVS twisted pair line is used to

other lines.

2. Don

t mount the emergency start/abort switch in a condensation, high temperature, greasy, humid or erosive

environment.

3. Disconnect the power during wiring procedures, and don

t connect it to a power source until you are sure it is

correctly wired.

4. You need to crush the organic glass with a hard object first when you want to press the button.
5. The organic glass is disposable goods, you need to replace a new one after the organic glass was crushed.
6. Don

t mount or regulate the emergency start/abort switch without professional guidance.

Address

3F, Guangcai New World Building, Nanshan Road, Nanshan District, Shenzhen, 518054, P.R.China

Tel

+86(755)86226969

Fax:

+86(755)86223939

Http://www.fhsjdz.com

The purpose of the QM-AN-965K Emergency Start/Abort Switch is
to provide an emergency start/stop control signal for the gas
extinguisher. During normal running, the RUN LED indicator lights
up. When the protected area is on fire, crush the organic glass
which is printed

START

and press the start button to send an

emergency start signal to the gas extinguisher, which turns on the
solenoid after a preset delay to activate the fire extinguishers. If the
fire in this area is put out before the extinguisher activates or it is a
false alarm, crush the organic glass which is printed

STOP

and

press the stop button to send an emergency stop signal to the gas
extinguisher to stop the delay period and prevent the extinguisher
from needlessly activating.