Instruction manual of QM-AN-965K Emergency Start/Abort Switch
------
Please read this manual carefully before installing and using the product
-----
I. General description
II. Technical parameters
1. Operating voltage: 24VDC (20VDC
~
28VDC)
2. Operating current:
<
30mA
3. Capacity of the output control contact: 2A@DC24V
4. Operating environment: Indoor, temperature:
-
10
℃~
+55
℃
Relative humidity:
≤
95% (
40
℃±
2
℃
, without condensation)
III. Instructions
1. Installation dimension of the QM-AN-965K Emergency Start/Abort Switch
2. Schematic circuit diagram
3. Terminal description
QM-AN-965K
JB-QBL-QM300/4
JB-QBL-QM200
JB-QB-QM200/4
Leading-out
Terminal
No.
Terminal
function
Leading-in
Terminal No.
Of the zone
control
terminal
board
Terminal
function
Leading-in
Terminal No.
Of the main
control
board
Terminal
function
Leading-in
Terminal No.
Of the zone
control
board
Terminal
function
1
GND
1
AGND
GND
(Between 18
and 19)
AGND
32
AGND
2
24V
6
+24V
1
+24V
31
+24V
3
STOP/NO1
1
AGND
GND
AGND
6
AGND
4
STOP/NO2
2
STOP
19
Emergency stop
control signal
5
STPB
5
START/NC1
5
START
17
Emergency start
control signal
1
STRB
6
START/NC2
6
+24V
1
+24V
2
+24VK
IV. Precautious
1. The minimum 1.5mm
2
BV line is used to supply power; the minimum 1.0mm
2
RVS twisted pair line is used to
other lines.
2. Don
’
t mount the emergency start/abort switch in a condensation, high temperature, greasy, humid or erosive
environment.
3. Disconnect the power during wiring procedures, and don
’
t connect it to a power source until you are sure it is
correctly wired.
4. You need to crush the organic glass with a hard object first when you want to press the button.
5. The organic glass is disposable goods, you need to replace a new one after the organic glass was crushed.
6. Don
’
t mount or regulate the emergency start/abort switch without professional guidance.
Address
:
3F, Guangcai New World Building, Nanshan Road, Nanshan District, Shenzhen, 518054, P.R.China
Tel
:
+86(755)86226969
Fax:
:
+86(755)86223939
The purpose of the QM-AN-965K Emergency Start/Abort Switch is
to provide an emergency start/stop control signal for the gas
extinguisher. During normal running, the RUN LED indicator lights
up. When the protected area is on fire, crush the organic glass
which is printed
“
START
”
and press the start button to send an
emergency start signal to the gas extinguisher, which turns on the
solenoid after a preset delay to activate the fire extinguishers. If the
fire in this area is put out before the extinguisher activates or it is a
false alarm, crush the organic glass which is printed
“
STOP
”
and
press the stop button to send an emergency stop signal to the gas
extinguisher to stop the delay period and prevent the extinguisher
from needlessly activating.