SANJIANG GB9221 Series Instruction Manual Download Page 5

GB9221 series instruction manual

-4-

by the alarm controller or provided by the output module.

3)Output line connection:

a) Line output

This interface is used to extend power amplifier or transfer audio

signal to other audio equipment. When the machine cannot meet the needs of field
application, power amplifier can be extended through this interface. The
connection line with the power amplifier should adopt high-quality shielded wire.
b) Fixed voltage output Fixed voltage output is power amplifier output, which
can be directly connected with fixed voltage speaker or broadcast circuit through
GB9231/GB9232 broadcast divider. RVS double twisted copper core wire above
1mm² should be used for fixed voltage output line. The line diameter should be
increased when long distance.

6 Installation and Debug

1)Correct connection shall be made according to the wiring instructions before

debugging.

2)The power LED(green) is on when power on.
3)Please do not connect any external circuit to the power amplifier before

troubleshooting. Please test if there’s short between the circuit and the chassis
using a multimeter or other test equipment to check the insulation resistance.It
is easy to damage machine when the power is turned on under short conditions.

4)When the circuit debug finished, preset volume should be set after the fire

alarm is triggered. After the preset volume is set, the machine can be used normally.

7 Instructions for use

1)Make sure the line connection is correct before use.
2)Output volume adjustment: The output volume can be changed by turning the front

panel “Volume Adjustment” knob.There are corresponding instructions. Note: It is
not allowed to change the volume in the emergency broadcast state.

3)Preset emergency broadcast volume: The emergency broadcast volume refers to

the volume under the emergency broadcast state. This volume should be manually preset
before use. It is effective after the fire alarm is triggered and cannot be manually
adjusted. The way to preset is as follows:

In non-emergency state, adjust the volume to the appropriate position, press on

the [volume adjustment]knob for more than 2 seconds,the alarm buzzer will keep ringing.
Then release the knob.

4)Fault alarm, noise elimination and reset:

◆ Overtemperature: when the internal transistor temperature exceeds the set

temperature limit (90℃), over temperature fault occurs. The indicator LED (yellow)
is always on.Cut off the power supply of the main circuit and send an alarm buzzer.When
the temperature is lower than the set value,system will automatically cancel the alarm
and restore.

Summary of Contents for GB9221 Series

Page 1: ...on manual before installation and use GB9221 series fire alarm broadcast amplifier Instruction manual suitable for 150W 300W 500W 2017 1 0 1 Overview 1 GB9221 series fire alarm broadcast amplifiers ar...

Page 2: ...42 Fire Broadcasting Host The output power could be 150W 300W 500W 4 GB9221 series fire alarm broadcast amplifiers assemble high quality power transformers internally The static power consumption is l...

Page 3: ...ower on off 2 volume adjustment LED indicator 3 volume adjustment knob 4 button self test 5 button silence 6 button monitor 7 over temperature fault LED indicator 8 overload fault LED indicator 9 outp...

Page 4: ...ed cable Pay attention to the order of N L E b Connect the backup power supply that meets the nominal requirements to the Standby Power terminal Pay attention to positive and negative polarity c Power...

Page 5: ...age machine when the power is turned on under short conditions 4 When the circuit debug finished preset volume should be set after the fire alarm is triggered After the preset volume is set the machin...

Page 6: ...Over temperature Over temperature because running under heavy load Reduce the output power or use after the temperature drops Over voltage Over voltage because light load Reduce the output amplitude a...

Page 7: ...48V 5A 15A GB9221 150W 150W 24V 3A 15A Table 1 1 Equipment model and parameter comparison table 11 Attached parts and components No Project Notes 1 Instruction manual 1 2 2 AC fuses 2 DC fuses See tab...

Reviews: