Chapter IV Others

4.1 Precautions

1) When connecting the line, attention shall be paid to the positive and negative polarity of the

power supply.

2) When in use, it should be noted that the chassis shall be grounded well.

3) In order to ensure stable operation of the system, the time interval of continuous switching

shall be greater than 10 seconds.

4)

If the linkage control with external control panel is required, ensure that the operating

frequency is not too fast.

4.2 Fault analysis and troubleshooting

See Table 2

Table 2 Fault analysis and troubleshooting

Fault

Possible cause

Solution

Emergency

start sound

is abnormal

Misoperation

causes

the

priority

of

the

emergency

source to be lower

Perform a recording delete operation until the

deletion is complete

The speaker connected to the

bus does not have a blocking

capacitor and the terminal

board is faulty.

Disconnect

the

bus.

During

standby,

the

multimeter measures the DC voltage of the

constant voltage output terminal above 50V,

otherwise it is considered damaged.Then replace

the terminal board to confirm.

The motherboard recording

module or audio transformer

is damaged.

Replace the motherboard

Amplifier failure

Replace the amplifier

Amplifier

failure

The amplifier itself is damaged

Replace the amplifier

The

terminal

board

is

damaged, causing the power

amplifier to report a fault.

Check whether the speaker is handled with a

straight block and replace the terminal block.

Summary of Contents for GB350E

Page 1: ...207 Fire Emergency Evacuation Broadcast GB350E Address 3 F Guangcai Xintiandi Mansion Nanhan Road Nanshan District Shenzhen Guangdong 518054 China Tel 86 755 86226969 Fax 86 755 86223939 Http www sanj...

Page 2: ...products produced by Shenzhen Fanhai Sanjiang Electronics Co Ltd Before using this device make sure you have read this manual in detail After commissioning and acceptance the manual shall be in charg...

Page 3: ...e operation 7 Interlock with control device by means of 485 communication mode 8 Equipped with auxiliary 24V emergency remote control wire interface 9 Reserved with standby 220V port for external conn...

Page 4: ...chassis greater than 50M DC500 V 12 Electrical strength AC input to the chassis leakage less than 10mA AC 1 250V 1 4 Logistic schematic diagram Fig 1 2 Logic schematic diagram External line 2 Externa...

Page 5: ...case of mains failure Constant voltage output Used for outputting the sound source and driving the external speaker to produce sound 485 A B Used to connect to communication port of external control...

Page 6: ...P4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 4 Wiring instruction 1 Power line connection 1 Connect 220V AC power cord to the mains 220V terminal and pay attention to the N L PE line sequence 2 Connect ba...

Page 7: ...xternal sound generating circuit and can be directly connected with a constant pressure horn or connected with an input output module 2 485 Output When connected to external control equipment connect...

Page 8: ...The EMER START Emergency Start indicator lamp is normally off and the system exits to the standby state The emergency broadcast is applicable to fire alarm When the emergency broadcast is triggered i...

Page 9: ...n 4 seconds to enter the recording waiting state Repeat the recording operation to exit the recording waiting state and the RECORD indicator will cyclically flash that is being on 0 5s and off 2 secon...

Page 10: ...When the fault alarm sounds press MUTE key or receive an external mute signal from 485 the Mute indicator is normally on and the buzzer is muted if there is a new fault in mute period the buzzer works...

Page 11: ...second and off for 2 second alternatively if the previous state is paused state the Play operation will be performed and the music indicator is normally on Note above operations can only be performed...

Page 12: ...arted will exit to the Registration state 3 10 Lock key function Lock key function is used to enable and disable the function of keyboard keys In the state of the lock key by default the power on rese...

Page 13: ...bnormal Misoperation causes the priority of the emergency source to be lower Perform a recording delete operation until the deletion is complete The speaker connected to the bus does not have a blocki...

Page 14: ...e product 1 copy Line sleeve 6 pcs Door lock and keys 1 Power line 1 Handheld microphone 1 pcs Statement This manual may change with the product upgrade without further notice subject to the product i...

Reviews: