SEC61X 

SERIES EEV 

CONTINUED

QUICK START GUIDE: 

 

2

3

Setting the System Refrigerant in the Controller:

1. During operating status, press and hold             for 3 seconds and you’ll see the 

Pyd

 screen.

2. Press           until screen displays 5 which is the default password, then press            to enter the  

     parameters table list.

3. Press           so that 

2.Pr

 is displayed, then press            twice and you’ll see 

rFy

 which is the system  

    refrigerant menu.

4. Press                      to select the number code for your system refrigerant.

5. Press and hold            for 5 seconds to save your setting and you’ll see

 ---

 which confirms the setting is 

stored.

SAFTEY TIPS

0=R-22

5=R-507

10=R-513A

15=R-744(N20)  20=R-407F

25=R-455A

1=R-404A

6=R-1234ze

11=R-448A

16=R-32

21=R-124

2=R=410A

7=R-1234yf

12=R-449A

17=R-245fa

22=R-717

3=R-134a

8=R-290

13=R-452A

18=R-23

23=R-407H

4=R-407C

9=R-450A

14=R-744(CO2) 19=R-407A

24=R-454C

REFRIGERANT TABLE 

Sensors Installation:

Pressure transmitter/temperature sensor 
installed on the tube of evaporator outlet. 
If the system is divided into several  
evaporators, install pressure transmitter/
temperature sensor at each evaporator 
outlet.

1. Finish connecting wiring before turning on power.
2. The RUN port (compressor signal) is a passive 
    port. If you add a voltage, it may cause the controller     
    burn out.
3. When using a transformer, ensure minimum power  
    of 15 VA (for 1 cont 1 EEV).
4. Wire diameter: 28 to 16 AWG

12VAC/DC

15 VA

Temperature 

Sensor

Pressure 

Sensor

EEV