SEC61X
SERIES EEV
CONTINUED
QUICK START GUIDE:
2
3
Setting the System Refrigerant in the Controller:
1. During operating status, press and hold for 3 seconds and you’ll see the
Pyd
screen.
2. Press until screen displays 5 which is the default password, then press to enter the
parameters table list.
3. Press so that
2.Pr
is displayed, then press twice and you’ll see
rFy
which is the system
refrigerant menu.
4. Press to select the number code for your system refrigerant.
5. Press and hold for 5 seconds to save your setting and you’ll see
---
which confirms the setting is
stored.
SAFTEY TIPS
0=R-22
5=R-507
10=R-513A
15=R-744(N20) 20=R-407F
25=R-455A
1=R-404A
6=R-1234ze
11=R-448A
16=R-32
21=R-124
2=R=410A
7=R-1234yf
12=R-449A
17=R-245fa
22=R-717
3=R-134a
8=R-290
13=R-452A
18=R-23
23=R-407H
4=R-407C
9=R-450A
14=R-744(CO2) 19=R-407A
24=R-454C
REFRIGERANT TABLE
Sensors Installation:
Pressure transmitter/temperature sensor
installed on the tube of evaporator outlet.
If the system is divided into several
evaporators, install pressure transmitter/
temperature sensor at each evaporator
outlet.
1. Finish connecting wiring before turning on power.
2. The RUN port (compressor signal) is a passive
port. If you add a voltage, it may cause the controller
burn out.
3. When using a transformer, ensure minimum power
of 15 VA (for 1 cont 1 EEV).
4. Wire diameter: 28 to 16 AWG
12VAC/DC
15 VA
Temperature
Sensor
Pressure
Sensor
EEV