background image

Merlin GDP4

 

 

 

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

Rev: 05 Date: 08-01-18

  

4  

 Operation Instructions  

3.1 

How to turn the system on and off 

1.  To turn the system on press reset to start the testing sequence. 

2.  The system will close the solenoid valve when an emergency stop has been pressed, gas has 

been detected or any alarm signal has been triggered. 

 

3.2 

Explanation of LED status 

3.2.1 

Power LED  

When the system is connected to the mains supply, the Power LED will illuminate. When no power is 
present, this LED will not light up.  

RED = OK  

OFF = No power to GDP4 or the fuse may not be intact. 

3.2.2 

Gas on LED  

On start up the Gas On LED will flash for one minute to check for gas being detected. If there is no gas 
detected or any other faults i.e. 

“EM STOP”, the gas valve will open and the green ‘Gas On’ LED will 

illuminate.

 

If the test is unsuccessful the relevant zone LED light will illuminate to indicate a fault.

 

GREEN = Gas On  
OFF = Gas Off  

3.2.3 

EM Stop LED  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate 
AMBER and the gas will be turned off. The EM Stop button must be re-set before restarting the system. 

OFF = OK  

AMBER = EM Stop button pressed 

3.2.4 

   Heat Detector LED 

 Under normal working conditions this LED is off. If the fusible link melts at 72 Degrees Celsius or higher, 
the LED will show AMBER and the Gas valve will turn off.  

3.2.5 

   Fire Alarm Panel LED 

 If the fire alarm has been activated, the LED will illuminate Amber and the gas will be    
 turned off. The Fire alarm panel must be re-set before restarting the system. 

 Off = OK 

 AMBER = Fire alarm activated! 

3.2.6 

Zones 1-4 LED 

Under normal working conditions this LED is GREEN. If the external Merlin detector connected detects 
the low level alarm this will show AMBER. If the external Merlin detector connected detects the high 
level alarm this will show RED and the gas solenoid valve will close. 

 

Explanation of LED Status 
  

 OK (Green) LED 

 Green 

– No gas detected. 

 

Low (Amber) LED 

 Amber 

– Low Level Alarm 

 

High (Red) LED 

 Red 

– Alarm! 

 

 

Summary of Contents for Merlin GDP4

Page 1: ...Merlin GDP4 Product Data Sheet Rev 05 Date 08 01 18 1 Gas Safety Products Merlin GDP4 Installation operating and maintenance Read these instructions carefully before operating or servicing...

Page 2: ...8 BMS Connections 3 2 9 Sounder Alarm 3 2 10 Internal Buzzer 3 2 11 Mute 3 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 3 2 1 Power LED 4 3 2 2 G...

Page 3: ...G Other detector types are available 2 5 Remote emergency shut off buttons The terminal for remote emergency shut off buttons is detailed on the circuit board as EM REMOTE These connections are linked...

Page 4: ...as On OFF Gas Off 3 2 3 EM Stop LED If an emergency shut off button either remote or on the panel is pressed the LED will illuminate AMBER and the gas will be turned off The EM Stop button must be re...

Page 5: ...ther or not 230V is being sent to the solenoid There is a dip switch located on the inside facia of the Merlin GDP4 labelled BMS SEL This is factory set in the off position which signals the BMS on ga...

Page 6: ...DC power supply purchased separately 7 Remote EM Stop buttons purchased separately VOLT FREE INPUT 8 Fusible Links purchased separately VOLT FREE INPUT 9 Fire panel Supplied by others VOLT FREE INPUT...

Page 7: ...l household waste but kept separate for the treatment recovery and recycling of the materials used Please contact your supplier or local authority for details of recycling schemes in your area CONTACT...

Reviews: