background image

Merlin CO2 Detector C1 

 

 

 

 

 

 

            User Guide 

 

 

 

Rev: 08  05-19

 

5  

4

 

Specifications 

 

Power Supply  230VAC, 50-60Hz (Max 2VA) 

Gas Sensor 

Carbon Dioxide: Non-Dispersive Infrared Detector (NDIR) 
ABC Logic Self Calibration 

CO2 Measuring Range  0-5000ppm (Resolution: 1ppm) 

Accuracy @ 25°C (77°F)  ±6% Reading 

Warm Up time   1 Minute 

Switch Over Relay Output 

Model: 1500ppm 
230VAC 1A, 30VDC 2A Switching Current (resistive load) 
CO2 Alarm >1500ppm - Relay ON / <1450ppm - Relay OFF 
Model: 2800ppm 
230VAC 1A, 30VDC 2A Switching Current (resistive load) 
CO2 Alarm >2800ppm - Relay ON / <2750ppm - Relay OFF 
Model 4500ppm 
230VAC 1A, 30VDC 2A Switching Current (resistive load) 
CO2 Alarm >4800ppm - Relay ON / <4750ppm - Relay OFF 

Storage Conditions  -40~70°C (-40~158°F); 0~95%RH, non condensing 

Operation Conditions  -0~50°C (-32~122°F); 0~95%RH, non condensing 

Net Weight/ Dimensions  190g / 135mm(W)x95mm(H)x38mm(D) 

Instalment Standard  Wall mountable 

 

 

5

 

Circuit Board 

 

 

1. 

Mains Input 230V, L & N 

2. 

Alarm relay, volt free connection to Merlin system.  
Common, Normally Open and Normal Closed. 

 

 
 

Summary of Contents for Merlin 1500ppm

Page 1: ...Merlin CO2 Detector C1 User Guide Rev 08 05 19 1 Gas Safety Products Merlin CO2 Detector C1 1500 2800 4500 ppm User Guide Please read this guide carefully and retain for future use...

Page 2: ...5 19 2 Table of contents 1 General Information 3 1 1 Mounting the CO2 detector 3 2 Installation 4 2 1 Mains Supply 4 2 2 Alarm Relay 4 3 LED Indication Status 4 4 Specifications 5 5 Circuit Board 5 6...

Page 3: ...s 10 Years Do not apply lighter gas or other aerosols to the detector this will cause extreme damage Never ignore your device when in alarm This device requires a continual supply of electrical power...

Page 4: ...tically switch back once the levels have dropped 3 LED Indication Status Model CO2 Detector 1500ppm Low Green LED Good air quality CO2 900ppm Medium Amber LED Moderate air quality 900ppm CO2 1200ppm H...

Page 5: ...rm 1500ppm Relay ON 1450ppm Relay OFF Model 2800ppm 230VAC 1A 30VDC 2A Switching Current resistive load CO2 Alarm 2800ppm Relay ON 2750ppm Relay OFF Model 4500ppm 230VAC 1A 30VDC 2A Switching Current...

Page 6: ...ly remove any accumulated dust from the outer enclosure once a month NEVER use detergents or solvents to clean your device this may permenantly or temporarily damage the gas sensing elements NEVER spr...

Page 7: ...Merlin CO2 Detector C1 User Guide Rev 08 05 19 7...

Page 8: ...r be liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due...

Reviews: