4.2 AUTOMATIC PROPORTIONAL CONTROL WITH A
P$
SIGNAL FROM AN EXTERNAL
ANALOGUE SENSOR (CO2, TEMPERATURE OR RELATIVE HUMIDITY)
4.2.1 Features
In this case, the equipment is used to regulate the air volume in accordance with the value measured by
an external sensor.
The external sensor must emit a
P$
analogue sensor.
With 0-10V input the input voltage values cannot be adjusted.
It is possible to change the behaviour of the proportional output by modifying the value of the LSP, HSP,
CrL3 and CRH3 paramaters.
In this case, some of the parameters configured in the frequency inverter must be re-programmed in the inverter
to avoid exceeding the overpressure value established by the relevant regulations. Access the programming
mode (steps 1 and 2 in section 2.2) and then perform the following configuration changes:
-
Press
ENTER
and rotate the wheel anti-clockwise un
til “
SEt-
” appears on the screen.
-
Press
ENTER
and rotate the wheel anti-
clockwise until “
LSP
” appears on the screen.
-
Press
ENTER
and rotate the wheel until the necessary value appears for the
“Minimum frequency in
Hz
” parameter. Press
ENTER
to confirm the value entered. If this value is different to the previous one,
the display should flash.
-
Press
ESC
to exit the “
LSP
” parameter.
-
Rotate the wheel until ”
HSP
” appears on the screen
-
Press
ENTER
and rotate the wheel until the necessary value appears for
the “
Maximum frequency in
Hz
” parameter. Press
ENTER
to confirm the value entered. If this value is different to the previous one,
the display should flash.
-
Press
ESC
to exit the “
HSP
” parameter.
-
Press
ESC
to exit the “
Set-
” menu.
-
Follow the method used to configure the two initial parameters until all of the parameters in the following
table have been configured:
MENU
Parameter
Value
Comment
I_O-
CrL3
7.2
Minimum reference value (mA)
I_O-
CrH3
14.4
Maximum reference value (mA)
Ctl-
Fr2
AI3
Current type reference (mA)
FUN-
PI-
PIF
No
Disable de PI function
-
Press
ESC
to exit the “
CtL-
” menu.
-
Keep
ESC
pressed down for 2 seconds until the 3 mode leds light up in sequence. It is now in
RUN
mode, available for automatic inverter operation.
Summary of Contents for VFTM IP21
Page 1: ...VFTM...
Page 2: ......
Page 47: ...47 Fig 2 1 Fig 2 2...
Page 48: ...48 Fig 2 3 Fig 2 4...
Page 49: ...49 Fig 3 1 Fig 3 2...
Page 50: ...50 Fig 3 3 Fig 3 4...
Page 51: ...51 Fig 4 1 Fig 4 2...
Page 52: ...52 Fig 4 3 Fig 4 4...
Page 53: ...53 Fig 5 1 Fig 5 2...
Page 54: ...54 Fig 5 3 Fig 5 4...
Page 55: ......