background image

 

 

OPERATING INSTRUCTIONS 

11.

 

Switch on the controller by pressing down the Red ON/OFF Rocker Switch which will 
illuminate when switched on. 

12.

 

REB 6, REB 8, REB 10, REB 12 and REB 16 only:- The controller has a boost start function and 
when switched on will start the fan running on full speed for approximately 10 seconds.  
Thereafter the speed will be determined by the position of the control knob. 

13.

 

Rotating the control knob fully clockwise will increase the speed of the fan from a factory 
pre-set minimum to full speed with infinitely variable control. 

14.

 

The minimum speed is pre-set and does not normally need adjusting. 

15.

 

REB 6, REB 8, REB 10, REB 12 and REB 16 only:- The controller has a thermal overload relay 
(terminals are designated TP) controlled by thermal protectors in the fan(s).  When the fan 
thermal protectors trip, (terminals in the fan are also designated TP), the relay switches the 
controller off to prevent the fan starting automatically in the event of the thermal 
protector(s) cooling and making the circuit again.  When this happens the red trip light 
switch is illuminated.  To reset push the reset button positioned near to the trip light. 

16.

 

IMPORTANT NOTE – REB 1, REB 3 and REB 5 only:- The controller does NOT have a thermal 
overload relay and as a consequence the common (U2 – motor live 230V) conductor is 
shown on the wiring diagrams routed via the thermal protector(s) in the fan(s) (terminals in 
the fan are designated TP).  In the event of the thermal protectors overheating, the power to 
the motor is cut; however upon the fan sensors cooling then the fan motor can remain live.  
To comply with European legislation EN 60335-2-80:2005, when connected to REB 1, REB 3 
or REB 5 controllers, in-line duct fans which incorporate self-resetting thermal protectors 
must be separately protected from automatic re-start. 

TROUBLESHOOTING 

17.

 

If your fan does not start (REB 6, REB 8, REB 10, REB 12 and REB 16 only) – 

ensure that the 

thermal protection (TP) relay has been correctly wired to the fan thermal sensors. 

18.

 

If your speed controller does not appear to vary the fan speed.

 

T

he voltage regulation 

function can be checked by measuring for a change in Voltage across terminals U1 and U2 
with the fan connected.  THERE WILL BE NO MEASUREABLE CHANGE IN VOLTAGE IF THE FAN 
IS NOT CONNECTED.  The fan may be replaced with an alternate load such as a lamp which 
will also provide a visual check that there is a variable voltage at the controller output. 

19.

 

To ensure that the fan is operating correctly

.

 

T

he controller could be temporarily removed 

from the system by wiring the fan directly to an isolator.  Please note that the wiring will 
differ to those diagrams contained herein and that the wiring diagram in the instruction 
booklet that was supplied with the fan should be followed instead. 
 

EC DECLARATION OF CONFORMITY 

Herewith we declare that the fan speed controller designated below, on the basis of its design and 
construction in the form brought onto the market by us is, in accordance with the relevant EC 
Council Directives on Electromagnetic Compatibility.  If alterations are made to the apparatus 
without prior consultations with us, this declaration becomes invalid.  We further declare that the 
equipment identified below may be intended to be assembles with other equipment/machines to 

Summary of Contents for REB 1

Page 1: ...1 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single phase induction motor fans...

Page 2: ...ous operation with the maximum rated current load listed in table 1 at 40 C ambient on single phase 230 Volts 50Hz supply 2 The normal equipment temperature range is 20 C to 40 C 3 The unit meets the...

Page 3: ...mon line the supply from controller terminal U2 only 6 If the controller is intended to control multiple fans then those fans must be of the same model size 7 All cable entries provided should be used...

Page 4: ...355 REB 5 HCBB 4 500 H HCBB 6 630 H HXBR 4 500 HXBR 6 630 2 TCBB 4 250 H TCBB 4 315 H TCBB 4 355 H TCBB 4 400 H TCBB 6 355 H TCBB 6 400 H TCBB 4 450 H TCBB 4 500 H TCBB 4 560 L TCBB 6 450 H TCBB 6 50...

Page 5: ...ERS SINGLE PHASE 230V 50Hz L Supply Live 230V 50Hz N Supply Neutral U1 Motor Control Variable Neutral U2 Motor Live 230V 50Hz A Auxiliary Permanent Neutral E Motor Supply Earth E WIRING DIAGRAM 1 WIRI...

Page 6: ...ITY WIRING DIAGRAM 8 For use with Other S P Fans where 3 wire control is NOT possible the controller must be used as a 2 wire regulator Please note that controller terminal AUX is unused Where the fan...

Page 7: ...cooling then the fan motor can remain live To comply with European legislation EN 60335 2 80 2005 when connected to REB 1 REB 3 or REB 5 controllers in line duct fans which incorporate self resetting...

Page 8: ...part is defective the product will be repaired or at the company s discretion replaced without charge provided that the product has been installed in accordance with the enclosed instructions and all...

Reviews: