S&P ES24V Quick Start Manual Download Page 1

 

 

 

 
 
 
 
The ES24V controls a ventilator to meet fresh air supply requirements 
while limiting operation during periods of extreme temperature and/or 
humidity. 
                                                                                                                                                         

INSTALLATION & OPERATION MANUAL 

 

CAUTION:

  

1.  READ AND SAVE THESE INSTRUCTIONS. 
2.  Before installation or maintenance, disconnect the power supply. 
3.  This control is for 24 VAC applications only. 
4.  All wiring must be done by qualified person(s) in accordance with 

all applicable codes & standards. 

5.  Indoor Use Only 

 

 

WIRING 

Use Copper Conductors Only 

Terminal 

Type 

Description 

24Vac 

Input: 24Vac input (50/60 Hz) 

24Vac 

Input: 24Vac common 

24Vac 

Input: Furnace Blower (Optional) 

24Vac 

Output: Furnace Blower (2A max) (Optional) 

F+ 

24Vac 

Output: Fresh Air Fan  (2A max) 

F- 

24Vac 

Output: Fresh Air Fan output - (2A max) 

D+ 

24Vac 

Output: Motorized  (2A max) (Optional) 

D- 

24Vac 

Output: Motorized Damper - (2A max) (Optional) 

H+ 

24Vac 

Output: Duct Heater  (2A max) (Optional) 

H- 

24Vac 

Output: Duct Heater output - (2A max) (Optional) 

 

 

MOUNTING 

 
Front Cover Removal 

Insert a flathead screwdriver into the slot 
on  the  right  side  of  the  controller  and 
apply  gentle  pressure  inward  and  up  so 
that  the  front  cover  disengages  from  the 
back cover. Pull the front cover up and to 
the left. 

 
 

 
 
 

Back Cover Mounting 

Locate the control on the mounting surface being sure to allow clearance 
for the necessary wiring connections. Mark the mounting hole locations and 
remove the back cover from the work space. Make the stripped/labelled 
wiring connections now. 

CAUTION: Be sure that no exposed portions of 

wires are touching.

 

 
If installing onto wood, mount the back cover with the provided screws. If 
installing onto drywall, drill pilot holes using a

 

7/32

 

drill bit (not

 

provided) 

and tap the provided drywall anchors into place. Mount with provided 
screws. 

NOTE: Velcro can be used to mount the control instead of screws 

if necessary.

 

 

Verify that wiring connections are correct and secure. 
 
Align the front cover with the 
back cover starting on the left 
side. Push the front cover 
towards the back cover in a 
“hinging” motion from the left to 
the right. 

CAUTION: Make sure 

the front cover is aligned properly 
with the back cover to avoid 
damaging the control.

 Press 

down until the front cover snaps 
securely into place.

 

 

Sensor Mounting 

The ES24V comes with a temperature sensor (26AWG, 2 wire) and 
humidity sensor (6P6C, telephone wire), both 10” long. Install the sensors 
at a location so that they will be exposed to the fresh air intake (ex: the 
fresh air ductwork). Drill 2, 3/4" diameter holes, spaced appropriately and 
install the sensors with the provided hardware. 

NOTE: the sensor wires can 

be extended up to 300 feet without deviation.

 Use appropriate duct tape to 

seal joints/openings as necessary.

 

 

DIMENSIONS (in) 

 

 

 

SCREEN DIAGRAM 

 

 
 
 
 
OPERATING MODES 
OFF Mode:

 All outputs are off. 

ON Mode:

 The Fresh Air Fan, Motorized Damper (if enabled), and 

Furnace Blower (if enabled) are on continuously. The Duct Heater 
will follow the user settings (see FUNCTION SETTINGS below). 

Eco Mode:

 

Eco Mode limits the Fresh Air Fan operation during 

periods of extreme temperature and/or humidity. The Fresh Air 
Fan, Motorized Damper (when enabled), Furnace Blower (when 
enabled), and Duct Heater (when enabled) will follow the user 
settings when the outside air temperature/humidity is within the 
user set limits (see FUNCTION SETTINGS below). 
 
The Fresh Air Fan will run for the user set amount of time/hour 
while the temperature/humidity limits are within range. The 
temperature/humidity sensors evaluate the fresh air conditions 
every 10 seconds. While the fresh air temperature/humidity is 
within the user set limits, the Fresh Air Fan/accessories will run 
per the user settings. When the fresh air temperature/humidity 
exceeds the user set limits, the Fresh Air Fan/accessories will turn 
off and engage a timer. The timer will run the fan for 5 minutes 
every 15 minutes in order to meet code requirements. 

NOTE: the 

Furnace Blower (if enabled) will not run during this check 
procedure to prevent cycling.

 The fan will continue this check 

procedure until the temperature/humidity limits are within the user 
set limits.

 

 
If Enabled (in SETUP): 
The Furnace Blower will be 

on: any time there is a call from “G” 

Input or any time the Fresh Air Fan is on (excluding the check 
procedure above). 
The Motorized Damper will be on anytime the Fresh Air Fan is on.   
The Duct Heater will be on any time the Fresh Air Fan is on and 
the set point > room tempe2°F.

 

(Motorized Damper, Furnace Blower, and Duct Heater are 
required to be enabled in SETUP)

 

BUTTONS 

Keys 

Description 

Mode 

Select the operating mode 

Set 

Confirm settings 

▲ 

Increase settings 

▼ 

Decrease settings 

S&P USA Ventilation Systems, LLC 
6393 Powers Ave 
Jacksonville, FL 32217 
ES24V 
Envirosense Ventilation Controller

 

 

Operating Modes: OFF, ON, or Eco 

Motorized Damper indicator 

Relative Humidity % 

Temperature (F or C) 

Thermostat integration indicator 

Fresh Air Fan indicator 

Duct Heater indicator 