5.1.2 HOW TO STORE THE UNIT AT THE DESTINATION
The unit is designed for floor mounting in a vertical position. The unit must be placed on a solid base with a maximum limit deviation of 3 mm per
2 m of length. The unit must be supported by an anti-vibration rubber pad with a minimum hardness of 50° Sha. The pad serves to reduce the
transmission of the dynamic effects of the unit to the substrate and at the same time to reduce the noise emissions emitted by the vibrating parts
of the unit. Washers are not included with the unit.
The unit must be positioned in the slope of max.
1° to the condensate drains at the operation side.
5.2 INSTALLATION PROCEDURE AND CONNECTION TO HVAC DISTRIBUTION LINES
All required dimensions and weights of the unit and accessories can be found in the "Technical data" chapter.
5.2.1 SAFETY INSTRUCTIONS FOR INSTALLATION
Follow all safety recommendations to prevent damage to the unit or personal injury. The technical characteristics of this manual must not be
changed. The motors of the unit must not be changed. The unit can be connected to the three-phase electric grid with alternating voltage 400 V /
50 Hz or to the single-phase grid with alternating voltage 230 V / 50 Hz depending on particular variant of the unit. For installation in accordance
with EC regulations, DUOVENT
®
COMPACT RV units may only be connected to the mains in accordance with the applicable regulations. The
device must be installed in such a way that, under normal operating conditions, it cannot come into contact with any moving or live part.
DUOVENT
®
COMPACT RV units comply with the applicable regulations for electrical equipment. Before carrying out any work on the device,
always disconnect the device from the power supply and secure the main switch of the power supply. energy against being switched
on again during service work
! Always use the appropriate tools. Use the device only for its intended purpose.
5.2.2 CONNECTION TO AIR DISTRIBUTION LINES
Arrangement diagram of components of Duovent
®
Compact RV units without mixing:
waste air
EHA
exhaust air
ETA
supply air
SUP
fresh air
ODA
m
ax
.
1°