3.4 OPERATION CONDITIONS

 

The unit can be used in rooms normal according to IEC 60364-5-51, resp. 

ČSN 332000-5-51 ed. 3, ČSN 332000-1 ed.2. The ambient 

temperature must be between -20 and +40 °C.

 

The unit can transport air without solid, fibrous, sticky, aggressive chemical and explosive additives. The maximum permissible supply air 
temperature must not 40 ° C. The maximum humidity of the air flowing through the unit is 17 g / kg s.v. (84 % r.h. at 25 °C).

 

If, due to the immediate climatic conditions, the humidity of the outdoor intake air reaches 100 % r.h. (wet steam), it is at the operator's discretion 
whether to keep the unit running with the risk of temporary separation of moisture on the internal parts 

of the unit (eg filters, flaps,…). This 

humidity cannot be the subject of a complaint.

 

3.5 DECLARATION OF CONFORMITY

 

This product type has been tested by the authorised person no. 227, Výzkumný ústav pozemních staveb 

– Certifikační společnost s.r.o., Pražská 

16, 102 21 Praha 10 

Hostivař, and a certificate has been issued to it. For a unit of the above type is issued a "Declaration of Conformity” within the 

meaning of Act No. 22/1997 Coll. as amended.

 

4. TRANSPORT, STORAGE, ACCEPTANCE

On the loading surface of the vehicle, the unit must be sufficiently secured against slipping and tipping over. The unit is wrapped in PE foil and 
placed on transport the pallet. The unit is fixed to the transport pallet by means of textile or plastic tie-ups.

 

During loading and unloading by the fork-lift the unit must be lifted suspended on the transport pallet. When transporting the unit supplied without 
the transport pallet it is necessary to support the unit on the underside over the entire surface to prevent damage and 

to pay attention to the 

condensate outlet opening on the underside of the unit

. During lifting by a crane, it is necessary to pass the ropes through the transport pallet 

or under the unit to prevent their slipping. THE UNIT CAN BE HANDLED ONLY BY SUPPORTING OR TYING UNDER THE UNIT FLOOR - THE 
UNIT CANNOT BE LIFTED BY THE CEILING OF THE UNIT OR OTHER PARTS (SUCH AS A/C FLANGES, EXCHANGER OUTLETS ETC.)

 

Ensure proper balancing of the transported unit. The ropes above the unit must be stretched to prevent damage. The outdoor variants of the units 
are fitted with transport profiles for safe passing of slings under the unit bottom.

 

The units must be stored in dry and dust-free areas where the ambient temperature does not fall below + 5 °C. The unit must be protected during 
storage against mechanical damage, dirt and corrosion caused by permanent condensation of water vapour on the surface of the unit. During 
storage, it is necessary to protect the units against snow, rain and other weather conditions (store in a covered warehouse).

 

When accepting the unit, it is necessary to check whether the product was delivered in the agreed design and extent, whether it was not 
damaged during transport, whether there is no condensed water under the plastic wrap (if there is moisture under the packaging, unpack the 
unit and dry in a covered dry place) . In case of damage during transport, the transferee must record the extent of damage in the Delivery Note, 
obtain and send photo documentation to S&P UK Ventilation Systems

 Ltd

Failure to comply with this procedure exposes the transferee to the 

risk

 

of rejection of the complaint by S&P UK Ventilation Systems

 Ltd

.

www.solerpalau.co.uk

 

!

 

CAUTION!

 

The unit shall not be transported above 
persons!

 

CAUTION!

 

The holes in the frame and legs are not

 

intended for the unit hinging.

 

CAUTION!

 

Units with direct evaporator (marked DX and DXr in the unit code) 
must be equipped with a mixing flap (marked MX in the unit code),

 

which ensures, if necessary, min. condenser/evaporator inlet 
temperature of +10 °C.

 

CAUTION!

 

For units with a direct evaporator (marked DX and DXr in the unit code), the 

design air flow through the unit must be observed 

when

 

operating the direct evaporator/condenser. It is acceptable to reduce the flow in cooling and heating mode by a maximum of 20 % of the 
design air flow. For proper operation of the direct evaporator, it is necessary to observe the necessary heat or cold consumption from the

 

heat exchange surface of the evaporator/condenser. If the design amount of energy is not consumed, the condensing unit / heat pump may 
report a fault in the pressure protections (LP, HP) of the cooling circuit and the condensing unit / heat pump may cycle in ON/OFF mode.

 

Summary of Contents for DUOVENT COMPACT DV

Page 1: ...INSTRUCTION MANUAL www solerpalau co uk DUOVENT COMPACT DV Ventilation unit with heat recovery...

Page 2: ...n Connection of electric heater Connection of water heater Connection of water cooler Connection of direct evaporator Connection of condensate drain Bypass and mixing flap Inlet and outlet flap 5 2 10...

Page 3: ...ation Warranty conditions The device must be installed by a professional air handling service company DUOVENT COMPACTDV incl controlsystemDVAV DCAV DCOP must be commissioned only by the Seller or by t...

Page 4: ...hat could affect safety and proper function are prohibited Installation and operating documentation must be available to the operator and service It is advisable to place it close to the installed uni...

Page 5: ...nit for ventilation of pool halls Order examples DUOVENT COMPACT DV 3000 DI DX MX KL G4 F7 F7 DVAV JH2 Unit size 3000 with electric heater direct evaporator bypass and mixing flap two stage filtration...

Page 6: ...INSULATION OF THE ANTIFREEZE PROTECTION CONTACT SENSOR WARNING DO NOT OPERATE THE UNIT WHILE CONSTRUCTION WORK IN PROGRESS AIR FLOW CALCULATION PLATE LOCATED AT FAN SUCTION PRESSURE ORIFICE PORT WARNI...

Page 7: ...0 182 DUOVENT DV 1200 521 992 312 80 2091 260 5 260 5 582 300 500 DUOVENT COMPACT DV 500 to 1200 under ceiling arrangement positions xH AH unit position drawn UNIT BOTTOM VIEW Exchanger outlets UNIT T...

Page 8: ...2 X3 L Y D Y Exchanger outlets D 20 D 1 2 1 2 DETAIL OF CONNECTING FLANGE INTEGRATED IN WALL PANEL 19 18 18 18 Condensate drains 152 152 152 21 www solerpalau co uk 40 A 150 B A B 150 F 157 42 42 X1 X...

Page 9: ...94 694 694 627 627 694 694 694 694 694 1085 1085 1085 1085 1085 1085 1085 DUOVENT COMPACT DV 1800 to 7800 floor arrangement positions xP AP unit position drawn X3 X1 X2 X E E X 1 2 1 2 19 18 18 18 Tra...

Page 10: ...00V 50Hz 3000 1238 927 1 8 1 4 89 1 3500 320 387 3000 DCA DCC 3000 DCA DX 21 8 21 8 21 3 21 3000 DI 15 22 4200 4200 DCA 4200 DCB 4200 DCA DCC 4200 DCA DX 4200 DI 29 8 22 30 2 20 5 29 8 3 400V 50Hz 420...

Page 11: ...ES EXCHANGER OUTLETS ETC Ensure proper balancing of the transported unit The ropes above the unit must be stretched to prevent damage The outdoor variants of the units are fitted with transport profil...

Page 12: ...is necessary to check the insulation of the HVAC piping in parts with a risk of condensation Condensate formed in the air duct can in unfavourable conditions spill into the interior of the unit where...

Page 13: ...tion box 5 1 2 HOW TO STORE THE UNIT AT THE DESTINATION The unit is designed for floor mounting in a vertical position positions marked xV in the unit code or horizontal position positions marked xP i...

Page 14: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with...

Page 15: ...let and outlet ports with respect to the position of the exchanger connection pipes Neck variants vertical arrangement viewed from unit operation side INLET OUTLET OUTLET INLET OUTLET OUTLET INLET INL...

Page 16: ...TLET OUTLET www solerpalau co uk INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET...

Page 17: ...INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET...

Page 18: ...n it is exceeded the operating thermostat opens and switches off the heater after cooling below 60 C the heater automatically switches on again Location of the release button under the cover on the un...

Page 19: ...nger connections it is necessary for example to hold the heat exchanger neck with a second wrench so that the tightening torque is not transmitted to the heat exchanger body Table of dimensions of wat...

Page 20: ...n screws on the heat exchanger collectors The heat exchanger can then be disconnected from the heating water distribution system and removed from the unit Max operating water temperature of water heat...

Page 21: ...the cooler must be vented after connecting and filling the system with cooling water The vent screws are located directly at the heat exchanger connection necks The vent screws are accessible either...

Page 22: ...specialist company It is mandatory to perform a Refrigerant leak test on the refrigerant circuit This test is performed only by a technician with the appropriate authorization according to the law 5 2...

Page 23: ...ING FLAP In the basic version each unit is equipped with a bypass flap of the plate heat exchanger BP The bypass is used for summer ventilation defrost control of the recuperation exchanger in the eve...

Page 24: ...on mode Location of mixing and bypass flap for DUOVENT 500 800 1200 units with MX mixing mode www solerpalau co uk ETA flap Mixing flap MX ODA flap Bypass flap BP Circulation flap C part 1 ODA flap Ci...

Page 25: ...uators 5 2 10 BASIC ACCESSORIES 5 2 10 1 CONDENSATE DRAIN TRAPS Condensate traps must be ordered as a separate item as they are not included with the unit Vacuum type siphon scheme SF P 300 bottom edg...

Page 26: ...ected piping Mixing units should be mounted on separate hinges using heating sleeves on the wall pipes or on an auxiliary structure When placed under the ceiling it is necessary to maintain control an...

Page 27: ...I C control system to the electrical distribution network is made by a separate supply cable which is not part of the delivery of the device www solerpalau co uk Ventilation unit with heat recovery DU...

Page 28: ...ts according to the set parameters in the automatic summer winter mode according to the outdoor temperature and time dependencies Manual mode selection is also possible The heater can be hot water con...

Page 29: ...otation of the fans the correct phasing of the damper actuators and mixing valves If the unit is equipped with a Digireg control system directly from the factory a SETPACK test package has been perfor...

Page 30: ...onnection to distribution lines Closing of all doors and service holes Any faults must be rectified before starting the unit for the first time 7 2 TRIAL OPERATION The material content of the comprehe...

Page 31: ...applicable regulations The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving or live part DUOVENT COMPACT DV units comply with t...

Page 32: ...NH IH2 JH2 MH2 NH2 263 295 263 365 KH LH OH PH KH2 LH2 OH2 PH2 263 295 263 295 1200 1200 all positions 420 365 365 420 ETA filter size ETA mm ODA filter size ETA mm Size of DUOVENT DV Vnom m3 h Neck...

Page 33: ...replace the entire unit or fan open the door by opening the locks by turning 90 The fan is located on rubber silent blocks Loosen the 4 nuts lift and remove the fan as shown in the following figure K...

Page 34: ...nitor the implementation of the measures taken Check the siphons for condensate drainage especially their permeability and tightness especially the tightness of the mounting on the unit and the tightn...

Page 35: ...l applicable standards and national and local building standards IF CLAIMING UNDER WARRANTY Please return the completed product carriage paid to your local authorised distributor All returns must be a...

Reviews: