Modifiez le style du titre
11.2. Change Parameters each evaporating
temperature set point
27
Parameter
Unit
Factory set
Tev≧-5℃
Tev≧-10℃
Tev≧-15℃
Tev≧-20℃
Tev≧-25℃
Tev≧-30℃
Tev≧-35℃
P08
MIN Low Pressure for Comp-ON
MPa
3.0
3.0
3.0
3.0
2.0
2.0
2.0
2.0
A/B01
MIN Low Pressure (Low Pressure Cut)
MPa
2.0
2.0
1.8
1.6
1.3
1.1
0.9
0.9
A/B02
Target Low Pressure
MPa
3.0
3.0
2.5
2.2
1.9
1.6
1.3
1.1
A/B05
MIN T°amb for Comp-ON
℃
-10
-25
-25
-25
-25
-25
-25
-25
A/B14
MAX T°amb for HP Calculation
℃
33
33
27
19
14
12
12
12
A/B15
Discharge Temp for HP Reduction Control
℃
115
115
115
115
105
105
105
105
A/B17
Target High Pressure Reduction
bar
1
1
1
1
2
2
2
2
A/B18
Reset Temperature for A15
℃
112
112
112
112
104
104
104
104
A/B19
Period for A18
min
3
3
3
3
2
2
2
2
C01
MIN Low Pressure (Low Pressure Cut)
MPa
2.0
2.0
2.0
2.0
2.0
1.5
1.5
1.5
C26
MIN T°amb for CHC-ON
℃
8
8
11
8
14
14
14
14
C27
MIN CLA/CLB Comp Speed for CHC-ON
Hz
40
40
40
35
35
35
35
35
C44
MIN T°amb for CHC-OFF
℃
5
5
8
5
10
10
10
10
C45
MIN Superheat for CHC-OFF
K
5
5
0.5
0.5
0.5
0.5
0.5
0.5
C52
MIN EEV Position
pls
40
40
150
150
150
150
150