1-3-4 Error History Display Mode
1) How to Change Mode
Press and hold down “UP” and “DOWN” keys together in the Clock Display Mode
to show the Block out Time Setting Mode. Press Enter key once to switch to the
Error History Display Mode. “Err0” will be displayed when the mode is switched
over.
2) How to Check Error History
The display repeats “Err*” -> “E***” -> “****” in the Error History Display Mode.
(“*” should be a number on the actual panel)
“*” in “Err*” shows the number of errors. The latest 10 times of errors can be
memorized.
The error number can be changed by pressing “UP” or “DOWN” key.
“*” in “****” shows the time that an error has occurred. For instance, if the display
shows “1446”, it means the time that an error occurred is 14:46 (2:46 p.m.). Date
of an error occurrence is not memorized.
Following shows the correlation of display and error history:
[Err0] Error occurred most recently
[Err1] Error occurred earlier than Err0
:
[Err9] Oldest error memorized in Error History
“*” in “E***” shows the generated error code.
Shown below is the list of the error codes.
E000 No error generated
E010 HP Inlet Temperature Thermistor wire break
E011 HP Inlet Temperature Thermistor short circuit
E012 HP Outlet Temperature Thermistor wire break
E013 HP Outlet Temperature Thermistor short circuit
E014 HP Ambient Temperature Thermistor wire break
E015 HP Ambient Temperature Thermistor short circuit
E016 HP Defrost Temperature Thermistor wire break
E017 HP Defrost Temperature Thermistor short circuit
E018 HP Discharge Temperature Thermistor wire break
E019 HP Discharge Temperature Thermistor short circuit
E020 Tank Thermistor A wire break
E021 Tank Thermistor A short circuit
E040 HP water outlet over temperature 1
E041 HP water outlet over temperature 2
E042 HP Outlet Temperature Thermistor detection error
E043 HP discharge over temperature 1
E044
HP Discharge Temperature Thermistor detection
error
E045 HP Defrost Thermistor detection error
E047 High pressure side error
E048 High ambient temperature defrost drive error
E070 Fan motor locked
E071 Fan motor revolution error
E073 Water circulation pump locked