S&C Instruction Sheet 1022-510
17
Testing Capacitor Bank Operation
Follow these steps to check control operation:
STEP 1.
Check that the control is operating properly. If the
faceplate LCD screen is scrolling through the
setpoints, go to step 2 below. If the LCD screen has
an error message:
(a) Connect your computer to the control and start
IntelliLink Setup Software. See Instruction Sheet
1022-530, “S&C IntelliCap
®
Automatic Capacitor
Control:
Setup
,” for more information.
R e a d t h e m e s s a g e ( s ) o n t h e
Troubleshooting>Event Log
screens, and take
appropriate action to correct any problems. See
Instruction Sheet 1022-550, “S&C IntelliCap
®
Automatic Capacitor Control:
Troubleshooting
,”
for more information.
(b) After error conditions are corrected, go to step 2.
STEP 2.
Check operation of the close/open relays:
(a) Make sure the AUTO/MANUAL switch is set to the
Manual
mode.
(b) Following your company procedures, use the
CLOSE/OPEN switch on the faceplate to operate
the capacitor bank. Verify visually that the
faceplate LCD screen correctly indicates each
bank-switch position.
T h e b a n k s t a t u s o n t h e L C D s c r e e n
(
**St at=Ba nkOf f l i ne**
or
**St at=Ba nk
Online**
) indicates the last requested operation,
which is normally the same as the present switch
position. The
**Stat=**
display will be blank until
the bank has been switched for the first time.
NOTICE
The capacitor bank cannot be closed for a period of 5
minutes after being opened . This delay provides time
for the capacitor charge to bleed off . For more details,
see Instruction Sheet 1022-540, “S&C IntelliCap Auto-
matic Capacitor Control:
Operation
.”
Setting the Control for Manual Operation
The IntelliCap control will only respond to a manual operation.
CAUTION
Be sure to leave IntelliCap control in
Manual
(not
Auto
)
mode until the software in the control has been config-
ured for this installation site .
This completes the IntelliCap control ha rdwa re
installation.
See Instruction Sheet 1022-530, “S&C IntelliCap
®
Automatic
Capacitor Control:
Setup
” for control configuration
instructions.
Installation
Summary of Contents for IntelliCap
Page 18: ...18 S C Instruction Sheet 1022 510 Wiring Diagrams ...
Page 19: ...S C Instruction Sheet 1022 510 19 Wiring Diagrams ...
Page 20: ...20 S C Instruction Sheet 1022 510 Wiring Diagrams ...
Page 21: ...S C Instruction Sheet 1022 510 21 Wiring Diagrams ...
Page 22: ...22 S C Instruction Sheet 1022 510 Wiring Diagrams ...
Page 23: ...S C Instruction Sheet 1022 510 23 Wiring Diagrams ...
Page 24: ...24 S C Instruction Sheet 1022 510 Wiring Diagrams ...