CWFL-6000 Series
16
0x0802
Alarm status
(
high 16-bit
)
MSByte
Bit7(MSb)
Retain
Bit6
Retain
Bit5
Retain
Bit4
Retain
Bit3
Retain
Bit2
Retain
Bit1
Retain
Bit0(LSb)
Retain
LSByte
Bit7(MSb)
Write administrator
parameter error
0
:
Correct
1
:
Error
Bit6
Write user parameter error
0
:
Correct
1
:
Error
Bit5
Ultra-high exhaust temp.
alarm
0
:
No alarm 1
:
Alarm
Bit4
Exhaust temp. sensor failure
alarm
0
:
No alarm 1
:
Alarm
Bit3
Ultra-low water temp alarm
0
:
No alarm 1
:
Alarm
Bit2
Ultra-low conductivity alarm
0
:
No alarm 1
:
Alarm
Bit1
Ultra-high conductivity alarm
0
:
No alarm 1
:
Alarm
Bit0(LSb)
High temp. system water
temp. sensor failure alarm
0
:
No alarm 1
:
Alarm
0x0803
Alarm status
(
low 16-bit
)
MSByte
Bit7(MSb)
Low temp. system water
temp. sensor failure
0
:
No alarm 1
:
Alarm
Bit6
Room temp. sensor failure
0
:
No alarm 1
:
Alarm
Bit5
Refrigeration system low
pressure
0
:
No alarm 1
:
Alarm
Bit4
Refrigeration system High
pressure
0
:
No alarm 1
:
Alarm
Bit3
High temp. water pump
overload
0
:
No alarm 1
:
Alarm
Bit2
Low temp. water pump
overload
0
:
No alarm 1
:
Alarm
Bit1
Compressor overload
0
:
No alarm 1
:
Alarm
Bit0(LSb)
Wrong phase and lacking
phase
0
:
No alarm 1
:
Alarm
LSByte
Bit7(MSb)
High temp. system ultra-high
water temp
0
:
No alarm 1
:
Alarm
5. Read/Write Registers(Use only when the external input
function is turned off)
Register address
Description
Range
Default
Unit
Remark
Symbol
0x0804
Chiller On/Off
0-1
--
0
:
On
,
1
:
Off
No
Summary of Contents for CWFL-6000
Page 1: ...CWFL 6000 INDUSTRIAL CHILLER USER MANUAL...
Page 19: ...CWFL 6000 Series 19 CWFL 6000...
Page 20: ...CWFL 6000 Series 20 21 22 23 24 29 29 MODBUS RS 485 30 33 34...
Page 21: ...CWFL 6000 Series 21 1 2 10 3 50Hz 60Hz 4 NORMAL NORMAL 5 100cm 50cm 6 7 8...
Page 22: ...CWFL 6000 Series 22...
Page 23: ...CWFL 6000 Series 23 1 2 3 4 1 E05 2 3 4 5 5 6 CWFL 6000 25 24...
Page 28: ...CWFL 6000 Series 28 E15 E15 E16 E16 E17 E17 E18 E18 E19 E19 E20 E20 E21 E21...
Page 34: ...CWFL 6000 Series 34 E01 E02 E01 E02 E05 E07 E03 40...