2. Detailed parameter setting is as below table:
Order
Code
Set item
Range
Factory
setting
Remark
1
F1
Set temp.
F7
~
F6/-20
~
40
25
Intelligent
mode /
Constant
temp mode
2
F2
Temp. difference values
-15
~
5
-2
3
F3
Cooling hysteresis
0.1
~
3.0
0.1
0.1 resolution
ratio
4
F4
Way of control
0
~
1
0
0 Constant, 1
Intelligent
5
F5
Set temp.
F7
~
F6/-20
~
40
30
Intelligent
mode /
Constant
temp mode
6
F6
Temp. difference values
-15
~
5
-2
7
F7
Cooling hysteresis
0.1
~
3.0
1
0.1 resolution
ratio
8
F8
Way of control
0
~
1
1
0 Constant, 1
Intelligent
9
F9
The highest set temp.
(
F10+1
)~
40
35
Constant
temp. mode
10
F10
The lowest set temp.
1
~(
F9-1
)
20
Min. 1,
Constant
temp. mode
invalid
11
F11
Ultra-high room temp.alarm
40
~
50
45
12
F12
Ultra-high water temp. alarm
1
~
20
10
13
F13
Ultra-low water temp. alarm
1
~
20
15
14
F14
Temp. alarm delay
0
~
30
5
Minute
15
F15
Sensor failure alarm delay
0
~
180
10
Second
16
F16
Water flow detection delay
of machine startup
0
~
180
5
Second
8
Summary of Contents for CW-7800 Series
Page 1: ...CW 7800 INDUSTRIAL CHILLER USER MANUAL...
Page 15: ...CW 7800 Series CW 7800 15...
Page 16: ...CW 7800 Series 17 18 19 20 24 24 25 26 16...
Page 17: ...CW 7800 Series 1 2 10 3 50Hz 60Hz 4 NORMAL NORMAL 5 100cm 50cm 6 7 8 17...
Page 18: ...CW 7800 Series 18...
Page 19: ...CW 7800 Series 1 2 3 4 1 E8 2 3 4 5 5 6 CW 7800 25 20 7 19...
Page 26: ...CW 7800 Series E01 E02 E01 E02 E05 E07 E03 40 26...