CW-6300 Series
10
Case 1: cooling water temperature is controlled by intelligent mode. Requiring
water temperature to be between 25
℃
to 31
℃
. When the set water temperature
is 3
℃
lower than the ambient temperature and ambient temperature remains
steady, the fluctuation will not exceed ±0.5
℃
. There will be an alert when water
temperature is 10
℃
lower or higher than target. (e.g. when ambient
temperature is 30.0
℃
, cooling water temperature is between 27.5
℃
to 26.5
℃
, if
ambient temperature is up to 30.5
℃
, water temperature will be between 28.0
℃
to 27.0
℃
.)
Case 2: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant at 28
℃
, and the fluctuate does not exceed ±2
℃
.
The ultrahigh water temperature alarm will be on when water temperature is 5
℃
higher than normal temperature, and the ultralow water temperature alarm will
be on when water temperature is 10
℃
lower than normal temperature.
Case 3: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant in 25
℃
, and the fluctuate does not exceed ±1
℃
.
The ultrahigh water temperature alarm will be on when water temperature is
higher than 30
℃
, and the ultralow water temperature alarmwill be on when
water temperature is lower than 10
℃
. (No matter what is the ambient
temperature, the cooling water temperature is constant between 24.0
℃
and
26.0
℃
)
4. Failure warning processing mode
When alarm occurs, the failure alarm code will be displayed on the upper right
corner of the LCD screen. In alarming state, the alarm sound could be
suspended by pressing any button, but the alarm display remains until the
alarm condition is eliminated.
20
F20
NO and NC setting of external
input function
NC
NC
NC
NC
21
F21
External input activation delay
0
0
0
0
22
F22
External input standby
activation delay
0
0
0
0
23
F23
Key lock of Chiller On/Off
1
1
1
1
24
F24
Self-starting after being
electrified
off
off
off
off
Summary of Contents for CW-6300
Page 1: ...CW 6300 INDUSTRIAL CHILLER USER MANUAL...
Page 19: ...CW 6300 Series 19 CW 6300...
Page 20: ...CW 6300 Series 20 21 22 23 24 29 MODBUS RS 485 30 33 34...
Page 21: ...CW 6300 Series 21 1 2 10 3 50Hz 60Hz 4 NORMAL NORMAL 5 50cm 30cm 6 7 8...
Page 22: ...CW 6300 Series 22...
Page 23: ...CW 6300 Series 23 1 2 3 4 1 E05 2 3 4 5 5 6 CW 6300 25 24 7...