SAMWON ENG CO.,LTD                 SU-105 Controller User Manual                                      Page 

2/3

 

To change hysteresis, press SET key for longer than 5 seconds. Release the key when  

  the display unit shows diF. 

Set the configuration as following using Up and Dn keys.

 

User 

setting

 

 

Item

 

Setting

  

        Description

 

diF  0.1~9.9 

 Prevent relay vibration from hysteresis  

Store the setting in memory by pressing the SET key for longer than 5 seconds.

 

Description of ON/OFF control based-on hysteresys value 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

User 

setting 

 

Item

 

Setting

  

        Description

 

tyP 

 

Controls the cooler (Reverse output)

 

 

Controls the heater (Normal output)

 

 Cooler On/Off control

  

When the current temperature becomes higher than a configured temperature, the main 

  output relay turns on.

 

You can use a delay timer to protect a compressor. 

 Heater On/Off control 

When the current temperature becomes lower than a configured temperature, the main 

  output relay turns on. 
Note: In general, the B contact of a relay is used for reverse output. In this case, be 
cautious since the contact B is ON even though the power to the unit is turned off. 
For example) 

        

    

Heater control                          

Cooler control 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF 

 

OFF 

 

 

OFF 

 

OFF 

   ON 

 

ON 

 

 

ON 

 

ON 

 

    SV=50.0,

diF

=5.0,

dLt

=0,

tyP

=H   SV=-25.0,

diF

=5.0,

dLt

=0,

tyP

=C 

 

 

 ▶

In order to change the delay timer setting, press SET key for longer than 5 seconds 

   while the display unit shows the current temperature. Release the key when the display 
   unit shows diF. Press SET key several times to select dLt.

 

 ▶

After selecting a value using Up or Dn key, press SET key to store the setting in the 

   memory. 
   Description: When the delay time expires, the output turns on.

 

User 

setting

 

 

Item

 

Setting

  

        Description

 

dLt 

0~240sec 

 Output become on after specified time 

 ▶

How the delay timer works 

 Case: the delay time is 0 second => the relay turns on as soon as output signal arrives. 

 

 
 
 
 
  
Case: the delay time is 5 seconds => the relay turns on after 5 seconds upon the arrival o 
output signal. 

 

 
▶The following diagram shows configurable items. Select an item by 
  pressing set key. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Make a note of the factory default settings before changing any one of them. Before 

  making any change, understand and verify the validity of your setting(s).

 

Invalid factory settings may require service from the manufacturer. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

50 

45 

-20 

-25 

 

9.Delay timer setting 

 

10.User configurable settings 

A

ux

 o

utp

ut 

setti

n

g

  

diF 

dLt 

tyP 

Normal/Reverse Control 

Hysteresis 

0.1℃~ 9.9℃ 

Delay time 

0~240sec 

Normal/Reverse selection 

C:Coller,H:Heater 

rSt 

Sensor input correction 

-50.0~+50.0 

Press set key when the display unit 
shows a current temperature 
 

Press set key for longer than 5 seconds 

to save the configuration. 

StH 

StL 

Upper limit temperature 

Temperature Range for each sensor

 

Keep pressing set key until you 

see 

StH

 on the display unit. 

Release the key when the 

display unit shows 

StH

※ 

diF

가 나타나면 다시 하세요 

 

Loc 

Lower limit temperature 

Temperature Range for each sensor 

 

Locking Function for user 

0:Release, 1:Locking 

SV 

OFF 

ON

 

15 

10 

SV 

OFF 

ON

 

15 

10 

SV 

ON 

OFF

 

15 

10 

SV 

ON 

OFF

 

15 

10 

tyP=H 

Heater(Normal)

 

tyP=C 

Cooler(Reverse)

 

hysteresis

 

diF=1.0

 

hysteresis

 

diF=2.0

 

 

8. Normal/Reverse output 

Delay time when

 dLt

=0 

Delay time when 

dLt

=5 

0sec 

5sec 

10sec 

Relay Off

                  

          

Relay On

 

Relay Off

             

Relay On

 

Aux Output(Alarm) 

Aux Output (Timer) 

Pro 

on 

Timer on setting 

0~999Min 

oFF 

Timer off setting 

0~999Min 

Alarm Setting Temp. 

Temperature Range 

for each sensor 

Fa

c

to

ry

 S

ettin

g

 I

tem

 

 

11.Factory default settings 

diF 

dLt 

tyP 

Alarm hysteresis 

0.1℃~ 9.9℃ 

Alarm delay timer 

0~240sec 

Aux output:Timer/Normal/Reverse Selection 

C:Cooler,H:Heater(C:Upper Alarm,H:Lower Alarm),t:Timer 

 

7.Hysteresis setting 

Turn off the power. Turn on the 

power while pressing set key. 

 

To go back to the top, press set key 

 

Press set key for longer than 5 seconds 

to save the configuration.

 

 