Digital Motor Protection Realy

DSP-C Series

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

   

 

 

 

 

 

   

 

 

   

 

   

 

   

 

 

 

 

 

   

 

 

       

 

   

 

 

 

 

 

 

 

   

   

   

   

   

     

   

   

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

   

 

 

   

   

   

 

 

 

   

 

   

   

 

 

 

 

 

   

 

   

 

   

 

 

 

 

   

 

 

 

 

 

 

 

 

   

 

   

 

   

 

 

 

 

 

 

   

 

 

   

   

   

   

 

   

 

 

 

   

 

   

   

 

 

 

 

 

   

 

 

 

 

 

 

   

 

   

 

   

   

 

 

 

 

   

 

 

 

   

   

 

 

 

 

   

 

 

 

 

   

 

 

 

 

 

 

 

 

   

   

 

   

   

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

   

 

   

 

 

   

   

 

 

 

 

 

 

   

 

 

   

 

 

   

 

 

   

 

 

   

   

 

   

 

 

 

 

 

   

 

 

   

 

 

   

 

   

   

 

   

   

   

 

 

 

 

     

 

 

 

 

 

 

   

 

 

 

 

     

 

   

 

 

 

   

 

 

 

 

 

 

 

   

 

 

 

   

 

   

 

   

 

 

 

 

 

   

 

 

Preset Key Operation

1. "SET" key

* Press "SET" Key to enter into setting mode, then "P0000"

(factory default password) is shown

* Move cursor from first digit to right end digit by pressing "CLR"key to

input password, like this manner make required digit by using "UP","DN"
key if it is customer's number , finally press once more,
then operator meets possible state for preset a number or character of mode.

* If there is no input for 15sec or pressing both "SET" and "CLR"key, it can

be entered into operating condition.

2. Changed
feature
of Setting Key

* After entering into posible state for preset , each key acts its job

as follows : SET---> backward direction, CLR--->foward direction,

UP.DN--->able to select number or character in preset mode.

* The previous mode based on setting mode is come out as pressing "SET"

key during doing a prest job

3. "SET" Key &
"CLR" Key/to
select MODE

* Possible to select Mode by using "SET" or "CLR" key

4. "UP" key &
"DN" Key/
Adjust

* Possible to preset required value as selection a character or number by using

UP/DOWN

5."SET" &
"CLR" Key/
Store

* The storage for preset data is completed by pressing both SET and CLR key

in the same time

6."CLR" key

* While each factor is rotated, one of rotated factor is fixed by pressing

"CLR" key

* After fixing a operating factor, the operator is able to rotate manual one by

one as pressing "UP"(forwardly), "DN"(reversely)

to check and/
or to change
preset value
of each mode
during the
operation

*Possible to check a value and a mode as pressing "SET" key once during

the operation

•preset value and mode are appeared alternatively
•next mode as pressing “CLR” Key or previous mode as pressing “SET” key
*Possible to change a preset value after entering into checking state if

the preset value of “OPSET” mode belonged to “CAB” mode group is “ON”/
factory default value is “OFF”

*Return to operating mode as pressing both “SET” and "CLR" key in the

same time or waiting for

Test/
Reset:"CLR"
Key

*to check if this relay is ready to work normally or not.
*"tESt" is appeared in case the operator presses test sw on the converter

or "CLR" key for 3 sec or more, then release pressed test sw or "CLR" key

*main trip(95-96-98) & aux trip(05-06-08) output will be trip after

counting down preset o-time(definite T-I)

*In case of display meter type, LED on the converter is flickering after a trip
*After making trip, press "CLR" key for the reset action

9

Summary of Contents for CCL

Page 1: ...or Protection Relay Digital Motor Protection Relay D I G I TA L S TA N D A R D P R O T E C T I O N Digital Motor Protection Relay www samwhadsp com New Leader Optimized Preventive Maintenance Solution...

Page 2: ...ing data base DB up based on 485 Modbus network Analyzing and managing DB DATA in order to check the motor condition and to make alarm in case of unstable condition able to preset alarm level for each...

Page 3: ...4 20mA output for load current insulation resistance measureemnt vibrated frequency detection through 4 20mA output from sensor RS485 or Ethernet communication Especially Current Resistance type can m...

Page 4: ...r current Phase loss load current Reverse phase load current Current unbalance Pre alarm Protection Locked rotor Shock Stall Short Circuit Ground fault Temperature Control ON OFF Load current Standard...

Page 5: ...Under current Protection Phaseloss load current Reverse phase load current Current unbalance Pre alarm Locked rotor Shock Stall Short Circuit Ground fault Temperature Control ON OFF Indication Load cu...

Page 6: ...put main 95 96 b 98 a aux 05 06 b 08 a b is selected in out mode factory default Control power is on unchanged output state 95 96 b 98 a aux 05 06 b 08 a TRIP operation state 95 96 a 98 b 05 06 a 08 b...

Page 7: ...ux trip output alarm RS 485 Modbus RTU External ZCT embedded if Z1 Z2 is not marked Input Output DSP COM DSP CCM E DSP CCM DSP CTM DSP CCTM DSP CSM Power Trip LED Test Reset 9Pin D sup to connect mete...

Page 8: ...han preset value is sensed Ground fault EC to ptotect over temperature sensed by PT100 8sec only for CCM PT CCL PT type Technical Specification DIV Description Load Current range 10 Type 70 Type With...

Page 9: ...EC 60255 5 Circuit Ground Circuit Circuit 1 2 50uS 5KV Control Circuits 1 2 50uS 5KV Power Realy output Level 4 4KV 1 MHz Burst Immunity Test IEC 61000 4 18 2 5KV Positive Negative under 2sec Electros...

Page 10: ...for preset data is completed by pressing both SET and CLR key in the same time 6 CLR key While each factor is rotated one of rotated factor is fixed by pressing CLR key After fixing a operating factor...

Page 11: ...eset a range to protect over current OC dt to preset starting trip delay time dEF dEF definite Inv inverse OtC to select time current chracteristics for Ot to preset operating trip delay time definite...

Page 12: ...ate additional factor besides basic factor to indicate running operation value in a order rOtA tEmP dC ALt AL to protect over temperature 8sec 1 150OC sensed by PT100 only for CCM PT CCL PT type to tr...

Page 13: ...Digital Motor Protection Realy DSP C Series T I Characteristic to protect over current Inverse Definite Samwha DSP 12...

Page 14: ...customer not used for external CT type Accessory External CT Cable ZCT DSP CABLE 12 DSP C1 DSP CC DSP C2 DSP C3 DSP C4 DSP CABLE 18 DSP CABLE 30 DSP CABLE 50 DSP ZCT XX 100mA 1 5mA XX Inner diameter...

Page 15: ...C Series wha Sam DSP Ltd ktTpp L1 L2 L3 65 70 75 80 85 90 95 100 Amp Ec Sec wha Sam DSP Ltd ktTpp L1 L2 L3 65 70 75 80 85 90 95 100 Amp Ec Sec Application Sequence Diagram Embedded ZCT Type External...

Page 16: ...Samwha DSP 15 Digital Motor Protection Realy DSP C Series 76 00 69 00 14 50 23 50 16 50 50 00 76 00 69 00 CUTTING HOLE SIZE 65 Wire Through Type Dimension Terminal Type Meter...

Page 17: ...Order CT Ratio Dimension Burden VA Class 1 0 3 0 3CT ithDSP Specification DSP 3CT Model CT Ratio 100 5A 150 5A 200 5A 300 5A 400 5A Class Burden VA Maximum Voltage Withstand Voltage Cable Length Max I...

Page 18: ...mA 100 250 600 1000 25 C 70 C 35 C 80 C AC 2000V 1min DC 500V 10MOhm 50 60Hz 10 Screw Fix 170 215 345 700 Order Form Item Reference Code Inner Diameter mm ZCT 30 50 80 120 DSP ZCT 30N DSP ZCT 50N DSP...

Page 19: ...18 DSP ZCT DSP ZCT Zero Phase Current Transformer 120 Zero Phase Current Transformer...

Page 20: ...m Optimized Preventive Maintenance Solution D I G I TA L S TA N D A R D P R O T E C T I O N DSP 91 69 693 2 3 TEL 031 454 3551 FAX 031 454 3552 HEAD OFFICE 69 LS ro 91beon gil Gunpo si Gyeonggi do Tel...

Reviews: