357
Installation
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
•
Check the condition of the product periodically.
- Check the installation site every 3 months and
perform anti-corrosion treatment such as R-Pro
supplied by SAMSUNG (Code : MOK-220SA) or
commercial water repellent grease and wax,
etc.,based on the product condition.
- When the product is to be shut down for a long
period of time, such as off-peak hours, take
appropriate measures like covering the product.
•
If the product installed within 500m of seashore,
special anti-corrosion treatment is required.
※ Please contact your local SAMSUNG representative
for further details.
Outdoor unit dimensions
(Unit: mm)
A Type
AC026RXADKG/AC035RXADKG
285
790
50
562
12
60
548
343
B Type
AC052RXADKG
880
49
310
638
364
660
12
26
C Type
AC071RXADKG
880
53
310
798
364
660
12
26
D Type
AC100RXADKG/AC100RXADNG/AC120RXADKG/
AC120RXADNG
998
977
537
528
620
940
330
384
360
675
E Type
AC140RXADKG/AC140RXADNG
620
330
384
360
1210
1185
940
567
558
675
Minimum clearances for the outdoor unit
When installing 1 outdoor unit
(Unit: mm)
300 or mor
e
1500 or mor
e
300 or
more
600 or
more
300 or
mor
e
2000
or more
1500
or mor
e
600
or mor
e
300
or more
1500
or mor
e
300 or
mor
e