Troubleshooting
If an error occurs during the operation, it is displayed on the outdoor unit PCB.
E-
30
SEG 1, 2
SEG 3, 4
Explanation
Display
High temperature of Discharge (Protection control)
SUMP COMP DOWN
Reverse phase error (Protection control)
COMP DOWN due to frozen Eva of indoor unit
Error of momentary power failure (disappears when the unit is Off/On)
Compressor Down due to protection control of high pressure sensor
Compressor Down due to protection control of low pressure sensor
In removing frost
Compressor Down due to protection control of condensation ratio
Error of OUT TEMP sensor (OPEN/SHORT)
Error level: Over 4.9V(-50°C), below 0.4V(93°C)
Error of COND TEMP sensor (OPEN/SHORT)
Error level: Over 4.9V(-50°C), below 0.4V(93°C)
Error of PWM Discharge TEMP sensor (OPEN/SHORT)
Detected when the outdoor temperature is over -10°C
Error level: Over 4.95V(-30°C), below 0.5V(151°C)
Error of liquid refrigerant pipe(cond out) TEMP (OPEN/SHORT)
Error level: Over 4.9V(-50°C), below 0.4V(93°C)
Error of OIL TEMP sensor (OPEN/SHORT)
Detected when the outdoor temperature is over -10°C
Error level: Over 4.95V(-30°C), below 0.5V(151°C)
Error of SUCTION TEMP sensor (OPEN/SHORT)
Error level: Over 4.9V(-50°C), below 0.4V(93°C)
Error of high pressure sensor (OPEN/SHORT)
Detected when the compressor is on
SHORT error when below 0.4V, OPEN error when over 4.2V
Error of low pressure sensor (OPEN/SHORT)
Detected when the compressor is on
SHORT error when below 0.4V, OPEN error when over 4.7V
Error of fixed compressor discharge sensor (OPEN/SHORT)
System Down caused by communication error after completion of tracking
Mismatching of the indoor unit numbers set with those communicated after completion of tracking
Error of float switch in indoor unit
Error of setting option switches for optional accessories
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Error about protection
control of outdoor unit
Errors about outdoor unit
sensor (OPEN/SHORT)
Communication errors
Remark
Summary of Contents for RVMC035EBM0