safety information
safety information
CAUTION SIGNS
Install the power cable and communication cable of the indoor and outdoor
unit at least 1.5m away from the electric appliances and install it at least 2m
away from the cable from the lightning rod.
•
Noise may heard depending on the electric wave though the cables.
•
Recommend that use a screened or shielded communication cable.
Install the outdoor unit within the angle of 25~55˚ depending on the building
height as below table.
Install the indoor unit away from lighting apparatus using the ballast.
•
If you use the wireless remote control, it may not operate normally.
Do not install the air conditioner in following places.
•
The place where there is mineral oil or arsenic acid.
Those parts may get damaged due to burned resin.
The efficiency of the heat exchanger may reduce or the air conditioner may be out of order.
•
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe
or air outlet.
The copper pipe or connection pipe may corrode and refrigerant may leak.
•
The place where there is a machine that generates electromagnetic waves.
The air conditioner may not operate normally due to control system.
•
The place where there is a danger of existing combustible gas, thinner or gasoline is handled.
•
The place where carbon fiber or flammable dust is.
•
The place where like spa and shore.
Changes in DVM PLUS
IV
comparing with conventional models(DVM PLUS
III
)
•
Use R410A refrigerant.
•
Check indoor units, MCU, distributor kits, etc which are connected with DVM PLUS
IV
are compatible with DVM PLUS
IV
or not.
•
Version of AVX
E and higher is available.
•
Make sure the combination method of outdoor units is different from DVM PLUS
III
.
•
The length of maximum piping, level difference, the quantity of connectable indoor units,
the installation at the outdoor joints and the outdoor unit combinations are different from
the conventional models.
•
Outdoor joint of gas side pipe should be installed horizontally due to the combination of
variable units when the height of the main pipe is lower than the outlet of the pipe of the
outdoor unit. The Installation of the liquid pipe and high pressure gas pipe are the same.
•
If the pipe length between outdoor units becomes 2m or more, install vertical pipe trap to
prevent oil stagnation in the pipes of the outdoor unit in the end of the module, in case of
the outdoor unit in the end of the module stops operating while part loading operation in
system. (Refer to page 26 for details.)
Building height Protective angle
Remarks
Below 20m
55˚
Below 40m
35˚
Below 60m
25˚
Building
Lightning rod
Protective angle: 25~55˚
RD@@@HHXG_IM_E_33140-3.indd 4