background image

11

ENGLISH

1  Push the supplied drain hose as far as possible over the drain socket.

2  Tighten the metal clamp as shown in the picture.

3  Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps.

4  Insulate the complete drain piping inside the building (field supply).  

If the drain hose cannot be sufficiently set on a slope, fit the hose with drain raising piping (field supply).

5  Push the drain hose up to insulation when connecting the drain hose to drain socket.

A-A’

Drain socket

Drain piping

Drain hose

Metal clamp

Large sealing pad

Tighten the clamp to the maximum until 
you can see eight holes. 

Drainpipe and drain hose installation

X

   When installing insulation in places and conditions below, use the same insulation that is used for high humidity conditions.

(FPMPHJDBMDPOEJUJPO
)JHIIVNJEJUZQMBDFTTVDIBTTIPSFMJOFIPUTQSJOHOFBSMBLFPSSJWFSBOESJEHF XIFOUIFQBSUPGUIFCVJMEJOHJTDPWFSFECZ
FBSUIBOETBOE
0QFSBUJPOQVSQPTFDPOEJUJPO
3FTUBVSBOUDFJMJOHTBVOBTXJNNJOHQPPMFUD
#VJMEJOHDPOTUSVDUJPODPOEJUJPO
5IFDFJMJOHGSFRVFOUMZFYQPTFEUPNPJTUVSFBOEDPPMJOHJTOPUDPWFSFE

e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.

5IFQMBDFXIFSFUIFQJQFJTJOTUBMMFEJTIJHIMZIVNJEEVFUPUIFMBDLPGWFOUJMBUJPOTZTUFN

Do not give the hose and upward gradient after the  
connection port. This will cause water to flow backwards 
when the unit is stopped, resulting in water leaks.

"JSWFOUJMBUJPO

Ceiling

Install air ventilation to drain condensate water smoothly.

Do not apply force to the piping on the unit side when 
connecting the drain hose. The hose should not be 
allowed to hang loose from its connection to the unit. 
Fasten the hose to a wall, frame or other support as close 
to the unit as possible.

6OEFSHSBEJFOU

Ceiling

If it is necessary to increase the height of the drainpipe, 

JOTUBMMUIFESBJOQJQFTUSBJHIUMZXJUIJOJODI
NNGSPNUIFESBJOIPTFQPSU*GJUJTSBJTFEIJHIFSUIBO
JODI NNUIFSFDBOCFXBUFSMFBLT

Support pieces

GU _N

Ceiling

1/100 or more

Check that the indoor unit is level with the ceiling by using the leveler.

Ceiling

Drain hose

JODI NNPSMFTT

JODI NN

 or more

Band joint

1/100 or more

JODI NN

PS

MFTT

Summary of Contents for PC4SUSMB

Page 1: ......

Page 2: ...thewarranty X Theairconditionershouldbeusedonlyfortheapplicationsforwhichithasbeendesigned theindoorunitisnotsuitabletobe installedinareasusedforlaundry X Donotusetheunitsifdamaged Ifproblemsoccur swi...

Page 3: ...nmental conditions If you must install the unit in such conditions first consult your dealer Avoid installing the air conditioner X In areas where it is exposed to direct sunlight Close to heat source...

Page 4: ...PPS VOJU X Make sure that the water dripping from the drain hose runs away correctly and safely X 5IF JOEPPS VOJU NVTU CF JOTUBMMFE JO UIJT XBZ UIBU UIFZ BSF PVU PG QVCMJD BDDFTT PU UPVDIBCMF CZ UIF V...

Page 5: ...IPME UIF EJTDIBSHF XIJMF DBSSZJOH UIF JOEPPS VOJU UP BWPJE UIF QPTTJCJMJUZ PG CSFBLBHF PV NVTU IPME UIF hanger plate on the corner and carry the indoor unit 6OJU 0 7700977 7701277 7701877 7702077 NN F...

Page 6: ...n JODI NN 0 Drawing of the indoor unit 5ZQF Type B Model 1 464 1 464 1 464 1 464 1 464 1 464 1 464 1 464 JODI NN 24 41 B JODI NN 22 03 _ 22 83 _ C JODI NN 1 87 0 89 D JODI NN 10 71 10 94 Sub duct conn...

Page 7: ...DFJMJOH BOE UIF JOEPPS VOJU CZ VTJOH UIF HBVHF of dimensions JY UIF JOEPPS VOJU TFDVSFMZ BGUFS BEKVTUJOH MFWFM PG UIF VOJU CZ VTJOH B leveler 3FNPWF UIF QBUUFSO TIFFU DPOOFDU UIF PUIFS DBCMFT BOE JOTU...

Page 8: ...VQQMJFE BOE TFU XJUI B QSF DIBSHF PG OJUSPHFO HBT JOTFSU HBT 5IFSFGPSF BMM JOTFSU HBT NVTU CF QVSHFE before connecting the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe 3...

Page 9: ...low for examples of incorrect flaring 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque t G UIF QJQFT SFRVJSF CSB JOH FOTVSF UIBU...

Page 10: ...te the gas side and liquid side pipe referring to the thickness according to the pipe size X OEPPS UFNQFSBUVSF PG BOE IVNJEJUZ PG MFTT UIBO JT UIF TUBOEBSE DPOEJUJPO If installing in a high humidity c...

Page 11: ...OH QPPM FUD VJMEJOH DPOTUSVDUJPO DPOEJUJPO 5IF DFJMJOH GSFRVFOUMZ FYQPTFE UP NPJTUVSF BOE DPPMJOH JT OPU DPWFSFE e g The pipe installed at a corridor of a dormitory and studio or near an exit that ope...

Page 12: ...BHF POMZ XIFO UIF BJS DPOEJUJPOFS JT JO DPPM mode Water leakage check part Hose t G B DPODFOUSBUFE ESBJO QJQF JT JOTUBMMFE SFGFS UP UIF HVSF CFMPX Concentrated drain pipe JODI NN or more 1 100 or more...

Page 13: ...GLISH 13 AA Bushing bracket installation If the conduit tube is used bushing bracket must be installed as shown in the picture to fix the conduit tube 1 2 3 Push 5 4 Click 1 conduit tube 2 conduit tub...

Page 14: ...S 6OJU 0VUEPPS 6OJU Wired Remote Controller 7 LJU K Ceiling wall mounted indoor unit 7_ or K ELCB Essential Installation 8 3 Power off before connecting any wires OEPPS 1 XJMM CF EBNBHFE XIJMF 7 7 TIP...

Page 15: ...FDJEF UIF DBQBDJUZ PG PS CZ CFMPX GPSNVMB 5IF DBQBDJUZ PG PS X 9 9 J 7 X The capacity of ELCB or MCCB ELB 7 Ai Sum of Rating currents of each indoor unit 7 Refer to each installation manual about the...

Page 16: ...le disconnection from the power supply must be incorporated in the fixed wiring 1 8 3mm X You must keep the cable in a protection tube X Keep distances of 2 50mm or more between power cable and commun...

Page 17: ...ion 4FU UIF FBDI PQUJPO TFQBSBUFMZ TJODF ZPV DBOOPU TFU UIF 3 44 TFUUJOH BOE JOEPPS VOJU JOTUBMMBUJPO TFUUJOH PQUJPO BU UIF TBNF UJNF PV OFFE UP TFU UXJDF XIFO TFUUJOH JOEPPS VOJU BEESFTT BOE JOTUBMMB...

Page 18: ...be selected in rotation On Dry On Dry 4FUUJOH BO NPEF 1SFTT PEF CVUUPO UP CF DIBOHFE UP NPEF JO UIF 0 TUBUVT On Fan 4FUUJOH 4 4 PQUJPO 1SFTT PX BO CVUUPO UP FOUFS 4 WBMVF 1SFTT JHI BO CVUUPO UP FOUFS...

Page 19: ...MVF BDI UJNF ZPV QSFTT UIF CVUUPO will be selected in rotation Off Fan Off Fan 18 Setting Heat mode 1SFTT PEF CVUUPO UP CF DIBOHF UP 5 NPEF JO UIF 0 TUBUVT Off Heat 4FUUJOH 4 4 NPEF 1SFTT PX BO CVUUPO...

Page 20: ...settheSEG9as0 theindoorunitwillmaintainpreviousRMCADDRESSevenifyouinputtheoptionvalueofSEG11 12 X YoucannotsetSEG11andSEG12asFvalueatthesametime OEPPS 6OJU 1 L F2 F1 2 N Option 4 4 4 4 4 4 YQMBOBUJPO...

Page 21: ...CF TFU UP A IPVS FWFO JG UIF 4 JT TFU UP FYFQU GPS PS X 8IFO TFUUJOH UIF PQUJPO PUIFS UIBO BCPWF 4 WBMVFT UIF PQUJPO XJMM CF TFU BT i w X 4 DFOUSBM DPOUSPM PQUJPO JT CBTJDBMMZ TFU BT 6TF TP ZPV EPO U...

Page 22: ...ls Indication Details Indication Details Indication Details Indication Details Indication Details Useof External room temperature sensor Minimizing fan operation when thermostat isoff 0 2 0 Disuse 0 D...

Page 23: ...ler Heatingsettingcompensation Removingcondensatedwaterin heatingmode EEVStepofstopped unitduringoilreturn defrostmode Motiondetectsensor Remote Controller Display Off Dry Off Fan Off Fan Off Heat Ind...

Page 24: ...JHOBM UIF TJHOBM GPS NPOJUPSJOH FYUFSOBM DPOUBDU DPOUSPM XJMM OPU CF PVUQVU 2 Fanisturnedoncontinuallywhentheexternalheateristurnedon 3 Fanisturnedoffwhentheexternalheateristurnedonwithcoolingonlyindo...

Page 25: ...F 2 5 C 4 3 6 F 2 C 4 3 6 F 2 C 4 5 4 F 3 C 5 4 5 F 2 5 C 5 4 5 F 2 5 C 5 6 3 F 3 5 C 6 5 4 F 3 C 6 5 4 F 3 C 6 7 2 F 4 C 7 6 3 F 3 5 C 7 6 3 F 3 5 C 7 8 1 F 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 S...

Page 26: ...H 4FUUJOH TFSJFT 4 w w 4FUUJOH TFSJFT 4 i w PU XBUFS IFBUFS JT UVSOFE PO BU UIF TBNF UJNF BT UIF IFBUJOH thermostatison andturnedoffwhentheheatingthermostatisoff F H 4FUUJOH TFSJFT 4 w w 4FUUJOH TFSJF...

Page 27: ...FO DIBOHJOH B EJHJU PG JOEPPS VOJU JOTUBMMBUJPO PQUJPO TFU UIF 4 BT A Ex When setting the buzzer control into disuse status Note SEG 3 4 5 6 8 9 additional information 8IFO UIF 4 JT TFU BT BOE GPMMPX...

Page 28: ...theairflowdirection Howtosetthetimers Howtocleanandreplacethefilters Note When you complete the installation successfully hand over the user installation manual to the user for storage in a handy and...

Page 29: ...Self diagnosis error display SSPS EVF UP PQFOFE 7 OE EFUFDUJPO SSPS EVF UP DMPTFE 7 OE EFUFDUJPO WB JO TFOTPS JT EFUBDIFE WB PVU TFOTPS JT EFUBDIFE 5IFSNBM GVTF FSSPS 0QFO X 0 NJE TFOTPS JT EFUBDIFE...

Page 30: ...DB68 03760 05...

Page 31: ...Mini 4way Cassette Type Series Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product...

Reviews: