11
ENGLISH
1 Push the supplied drain hose as far as possible over the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building (field supply).
If the drain hose cannot be sufficiently set on a slope, fit the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting the drain hose to drain socket.
A-A’
Drain socket
Drain piping
Drain hose
Metal clamp
Large sealing pad
Tighten the clamp to the maximum until
you can see eight holes.
Drainpipe and drain hose installation
X
When installing insulation in places and conditions below, use the same insulation that is used for high humidity conditions.
(FPMPHJDBMDPOEJUJPO
)JHIIVNJEJUZQMBDFTTVDIBTTIPSFMJOFIPUTQSJOHOFBSMBLFPSSJWFSBOESJEHF XIFOUIFQBSUPGUIFCVJMEJOHJTDPWFSFECZ
FBSUIBOETBOE
0QFSBUJPOQVSQPTFDPOEJUJPO
3FTUBVSBOUDFJMJOHTBVOBTXJNNJOHQPPMFUD
#VJMEJOHDPOTUSVDUJPODPOEJUJPO
5IFDFJMJOHGSFRVFOUMZFYQPTFEUPNPJTUVSFBOEDPPMJOHJTOPUDPWFSFE
e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.
5IFQMBDFXIFSFUIFQJQFJTJOTUBMMFEJTIJHIMZIVNJEEVFUPUIFMBDLPGWFOUJMBUJPOTZTUFN
Do not give the hose and upward gradient after the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
"JSWFOUJMBUJPO
Ceiling
Install air ventilation to drain condensate water smoothly.
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as close
to the unit as possible.
6OEFSHSBEJFOU
Ceiling
If it is necessary to increase the height of the drainpipe,
JOTUBMMUIFESBJOQJQFTUSBJHIUMZXJUIJOJODI
NNGSPNUIFESBJOIPTFQPSU*GJUJTSBJTFEIJHIFSUIBO
JODI NNUIFSFDBOCFXBUFSMFBLT
Support pieces
GU _N
Ceiling
1/100 or more
Check that the indoor unit is level with the ceiling by using the leveler.
Ceiling
Drain hose
JODI NNPSMFTT
JODI NN
or more
Band joint
1/100 or more
JODI NN
PS
MFTT