Samsung ND200HHXEA Installation Manual Download Page 25

E-

25

Troubleshooting

  If an error occurs during the operation, an LED flickers and the operation is stopped except the LED.

  If you re-operate the air conditioner, it operates normally at first, then detect an error again.

Detection of errors

LED Display on the receiver & display unit

LED Display

 

On      Flickering      Off

  If you turn off the air conditioner when the LED is flickering, the LED is also turned off.

  If you re-operate the air conditioner, it operates normally at first, then detect an error again.

Abnormal conditions

Indicators

Operating

Concealed Type

Green

Red

Standard Type

Power reset
Error of temperature sensor in indoor unit  

(OPEN/SHORT)

Displayed on appropriate 

indoor unit which is operating

Error of heat exchanger sensor in indoor unit 

Error of heat exchanger OUT sensor in  

indoor unit 

Error of outlet temperature sensor in  

indoor unit  

(OPEN/SHORT): For heat pump models only

Displayed on appropriate 

indoor unit which is operating

Error of outdoor temperature sensor 

Error of COND sensor 

Error of DISCHARGE sensor

Displayed on appropriate 

indoor unit which is operating 

Displayed on outdoor unit

1.  No communication for 2 minutes between 

indoor unit and outdoor unit (communica-

tion error for more than 2 minutes)

2.  Indoor unit receiving the communication 

error from outdoor unit

3. Outdoor unit tracking 3 minute error
4.  When sending the communication error 

from outdoor unit the mismatching of the  

communication numbers and installed  

numbers after completion of tracking.  

(communication error for more than  

2 minutes)

1.  Error of indoor unit: 

Displayed on the indoor unit 

regardless of operation

2.  Error of outdoor unit: 

Displayed on the indoor unit 

which is operating

AVXDU@@_IM_E_33764A-1_110621.indd   25

2011-06-23   오전 10:14:36

Summary of Contents for ND200HHXEA

Page 1: ...sibilities Thank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register Duct Type Series BIG duct ND HH E DB98 33764A 1 AVXDU _IM_E_33764A 1_110621 indd 29 2011 06 23 오전 10 14 37 ...

Page 2: ...t 10 Connecting the Refrigerant Pipe 10 Cutting Flaring the Pipes 11 Performing Leak Test Insulation 12 Drain pipe and Drain hose Installation 14 Wiring Work 18 Indoor Unit Setting 22 Additional Functions 23 Final Checks and User Tips 24 Troubleshooting 25 Option table 27 AVXDU _IM_E_33764A 1_110621 indd 2 2011 06 23 오전 10 14 29 ...

Page 3: ...ccessible to the general public This appliance should be installed according to the provided installation instruction When installing the air conditioner in a small room the measure not to exceed the dangerous density is needed When refrigerant leaks and exceeds the dangerous density suffocation may occur If any gas or impurities except R410A refrigerant come into the refrigerant pipe serious prob...

Page 4: ... work must be done by service agent or similarly qualified persons according to national wiring regulations and use only rated cable If the capacity of the power cable is insufficient or electric work is not properly completed electric shock or fire may occur Install the cables with supplied cables firmly Fix them securely so that external force is not exerted to the terminal board If the connecti...

Page 5: ...ue to the ballast of the lighting apparatus Do not install the air conditioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air conditioner may be out of order The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outle...

Page 6: ...ity may differ depending on the specifications User s manual Installation manual Pattern sheet Insulation cover pipe out Insulation pipe A Insulation pipe B Washer Clamp hose Flexible hose Cable tie Sleeve Rubber Insulation cover pipe in AVXDU _IM_E_33764A 1_110621 indd 6 2011 06 23 오전 10 14 29 ...

Page 7: ...ake service clean and repair the unit It is possible to install the unit at an height of between 2 2 2 5m from the ground if the unit has a duct with a well defined lenght 300mm or more to avoid fan motor blower contact Space requirements for installation service Construction Standard for Inspection Hole 1 In case the ceiling is textile Inspection hole dose not need 2 In case the ceiling is plaste...

Page 8: ...ø25 Power supply Communication connection Air discharge grille flange Air suction flange Hook 3 8 or M10 Selecting the Installation Location Continued 140X8 1120 1306 Suspension position 1188 Air inlet duct flange 1188 Air outlet duct flange Discharge side Suction side 1040 140X8 1120 34 1240 OD 32 35 470 660 647 598 29 93 22 209 236 385 100X2 200 914 Suspension position Unit mm AVXDU _IM_E_33764A...

Page 9: ...nsion bolts between two nuts Screw the nuts to suspend the unit Adjust level of the unit by using measurement plate for all 4 sides Since the diagram is made of paper it may shrink or stretch slightly due to temperature or humidity For this reason before drilling the holes maintain the correct dimensions between the markings Note For proper drainage of condensate give a 1 slant to the left or righ...

Page 10: ... A There are two refrigerant pipes of differing diameters A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper pipe must be clean has no dust The connection procedure for the refrigerant pipes varies according to the exit position of the pipes from the indoor unit as seen when facing the indoor in the A side Liquid refrigerant port Gas refrigerant port...

Page 11: ...r D mm A mm Flaretoolfor R410Aclutchtype Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 70 0 0 5 1 0 1 5 1 5 2 0 15 88 0 0 5 1 0 1 5 1 5 2 0 5 Check if you flared the pipe correctly There are some examples of incorrectly flared pipes below 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying t...

Page 12: ...onitrile Butadien Rubber separately around each refrigerant pipe Note Always make the seam of pipes face upwards 2 Wind insulating tape around the pipes and drain hose avoiding to compress the insulation too much 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes and electrical cables connecting the indoor unit with the outdoor unit must be fixed...

Page 13: ...ø22 23 ø25 40 ø28 58 32t ø31 75 ø38 10 ø44 45 ø50 80 25t 38t Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU You can contact the gas side and liquid side pipes but the pipes should not be pressed When contacting the gas side and gas side pipe use 1 grade thicker insulation Refrigerant pipe after EEV kit and MCU Install the gas side and liquid side pipes leave 10mm of space When ...

Page 14: ...lightly bigger than the external diameter of the drain hose port 4 Wrap the drain hose with the insulation drain as shown in figure and secure it Fix the flexible hose to the indoor unit with the supplied cable clamp securely Use the screwdriver to fix the flexible hose securely Note Inner diameter of the drain hose Give a slightly slant to the drain hose for proper drainage of condensate Fix the ...

Page 15: ...slope of 1 100 or more and fix it by hanger space of 1 0 1 5m 3 Install the air vent in the horizontal drain pipe to prevent water flow back to the indoor unit You may not need to install it if there were proper slope in the horizontal drain pipe Note 4 The flexible hose should not be installed upward position it may cause water flow back to the indoor unit With the drain pump Flexible hose Air ve...

Page 16: ...n air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent to prevent water flow back at the top of each indoor unit drain pipe With the drain pump Hanger Main drain pipe Individual air vent Main air vent Centralized horizontal drain pipe more than 1 100 slope 330mm or less 1 1 5m 100mm or more C...

Page 17: ...ain pump pumping 3 Testing the drainage Confirm that the water flows out through the drain hose 2 Reassemble the cover of water supply intake 6 Check drain water drops at the end of the drain pipe 4 Make sure there is no water leak at the drainage 5 Drain pipe Drain water drops The designs and shape are subject to change according to the model AVXDU _IM_E_33764A 1_110621 indd 17 2011 06 23 오전 10 1...

Page 18: ...communication when installing the wired remote control Power and communication cable connection WiringWork Connecting power for optional product When installing optional product make sure to follow below current capacity h Optional product is not supplied by manufacturer AC Below 2A AC Below 2A HOT T B 1 L 2 N Vc Vc Vw Vw POWER L VENTILATOR OPTION POWER N COIL ELCB MCCB ELB Indoor Unit 1 Outdoor U...

Page 19: ...installation manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units T coef 1 55 T Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Silver solder Selecting compressed ring terminal Norminal dimensions for c...

Page 20: ...oef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 h Calculation Installing with 1 sort wire 220 V 2 2 V 2 0 V 2 5 mm2 208 8 V Within 198V 242V 2 2 2 0 1 8 1 5 1 3 1 1 0 9 0 7 0 4 0 2 11 2 V it s okay 2 5 mm2 2 5 mm2 Installing with 2 different sort wire 220 V 1 4 V 1 2 V 2 5 mm2 209 5 V Within 198V 242V 1 4 1 2 1 8 1 5 1 3 1 1 0 9 0 7 0 4 0 2 10 5 V it s okay 4 0 mm2 4 0 mm2 ELCB or MCCB ELB AVXD...

Page 21: ...ction from the power supply must be incorporated in the fixed wiring 3mm You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication cable Maximum length of power cables are decided within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker ELCB or MCCB ELB should be considered more capacity if ma...

Page 22: ... the indoor unit address on the plan that you are to install and set the address according to the plan Setting RMC Address The SW03 and SW04 RMC switch is the address setting switch for controlling the indoor unit with the centralized controller You must set the SW03 SW04 and K2 switch when using the centralized controller You don t have to set the SW03 and SW04 RMC switch when not using the centr...

Page 23: ...10K11K12 No Function ON OFF SW06 K5 Heating CurrentTemperature Compensation 2 C 5 C K6 Filter Time 1 000 hours 2 000 hours K7 Hot Water Heater Not Use Use K8 K5K6K7K8 K1K2K3K4 No Function ON OFF SW05 K1 External room sensor Not use Use K2 Centralized controller Not use Use K3 K4 Drain Pump Not use Use g K1 OFF Heating mode Setting temperature compensation value 0 C Thermo OFF Fan OFF AVXDU _IM_E_3...

Page 24: ...tallation of the air conditioner you should explain the following to the user Refer to appropriate pages in the User s Manual 1 How to start and stop the air conditioner 2 How to select the modes and functions 3 How to adjust the temperature and fan speed 4 How to adjust the airflow direction 5 How to set the timers 6 How to clean and replace the filters When you complete the installation successf...

Page 25: ...er OUT sensor in indoor unit Error of outlet temperature sensor in indoor unit OPEN SHORT For heat pump models only Displayed on appropriate indoor unit which is operating Error of outdoor temperature sensor Error of COND sensor Error of DISCHARGE sensor Displayed on appropriate indoor unit which is operating Displayed on outdoor unit 1 No communication for 2 minutes between indoor unit and outdoo...

Page 26: ...ARGE 9 COMP DOWN due to 2nd detection of low pressure switch 10 Error of reverse phase 11 Compressor down due to 6th detection of freezing 12 Self diagnosis of condensation sensor G8 G9 13 Compressor down due to condensation ratio control Displayed on appropriate indoor unit which is operating Displayed on outdoor unit Error of float switch Error of setting option switches for optional accessories...

Page 27: ...ernal static pressure of the installation place is in When it is out of input the appropriate option code If you input the inappropriate option code error may occur or the air conditioner is out of order The option code must be inputted correctly by the installation specialist or service agent Static Pressure mmAq 5 10 15 20 25 28 Model Step Option code for indoor unit ND200HHXEA HIGH 015A17 15007...

Page 28: ... EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS AVXDU _IM_E_33764A 1_110621 indd 28 2011 06 23 오전 10 14 37 ...

Reviews: